Plan Review Notes
Plan Review Notes For Permit 09040215
Permit Number 09040215
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-17 11:55:58 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 4} NOTE: THE EMERGENCY LIGHTS MUST NOT BE WIRED TO THE
 TIME CLOCK (IE: HP 1&2) BUT MUST COMPLY WITH
 700.12(F)(4), 2005 NEC.*** THE CIRCUITS THAT IS NOW
 BEING USED FOR THE EMERGENCY LIGHTS ARE NOT FROM THE
 HOUSE PANEL IN VIOLATION 210.25 COMMON AREA BRANCH
 CIRCUITS
 BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY
 LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED
 ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED
 FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL,
 COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON
 AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT
 BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL
 DWELLING UNIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
 .