Plan Review Notes
Plan Review Notes For Permit 09040215
Permit Number 09040215
Review Stop M
Sequence Number 1
Notes
Date Text
2009-04-22 09:50:29REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
 1. PROVIDE EQUIPMENT SCHEDULE FOR PROPOSED NEW BATHROOM
 EXHAUST FANS. MECHANICAL PERMIT REQUIRED FOR THIS SCOPE
 OF WORK.
  
 2. UPDATE PLANS TO REFLECT COMPLIANCE WITH FBC 2007
 WITH 2009 SUPPLEMENT. THIS CODE IS IN EFFECT AS OF
 MARCH 1, 2009.
  
 NOTE: ELECTRICAL PLANS INDICATE POWER BEING PROVIDED
 FOR "FUTURE" SPLIT A/C SYSTEMS. SEPARATE PLANS,
 EQUIPMENT SCHEDULE AND COOLING LOAD CALCULATIONS WILL
 BE REQUIRED FOR THIS SCOPE OF WORK IF BEING DONE AT A
 LATER DATE. COOLING LOAD CALCULATIONS SHALL BE IN
 ACCORDANCE WITH FBC-B 13-607.AB.1.
  