| Plan Review Notes For Permit 09040215 |
| Permit Number |
09040215 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-22 09:50:29 | REVIEW #: 1ST **PLAN CHECK ONLY** | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | | | | 1. PROVIDE EQUIPMENT SCHEDULE FOR PROPOSED NEW BATHROOM | | | EXHAUST FANS. MECHANICAL PERMIT REQUIRED FOR THIS SCOPE | | | OF WORK. | | | | | | 2. UPDATE PLANS TO REFLECT COMPLIANCE WITH FBC 2007 | | | WITH 2009 SUPPLEMENT. THIS CODE IS IN EFFECT AS OF | | | MARCH 1, 2009. | | | | | | NOTE: ELECTRICAL PLANS INDICATE POWER BEING PROVIDED | | | FOR "FUTURE" SPLIT A/C SYSTEMS. SEPARATE PLANS, | | | EQUIPMENT SCHEDULE AND COOLING LOAD CALCULATIONS WILL | | | BE REQUIRED FOR THIS SCOPE OF WORK IF BEING DONE AT A | | | LATER DATE. COOLING LOAD CALCULATIONS SHALL BE IN | | | ACCORDANCE WITH FBC-B 13-607.AB.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|