| Plan Review Notes For Permit 09040215 |
| Permit Number |
09040215 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-24 11:45:02 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION | | | AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION) SHALL BE | | | REFERENCED. | | | | | | 4. SPECIFY THE INTERIOR FINISH MATERIAL IN TERMS OF | | | CLASS A, CLASS B, OR CLASS C FOR THE NEW WALL AND | | | CEILING. | | | | | | 5. ON SHEETS E1.0.1 AND E2.0.1, THE USE OF SMOKE | | | DETECTORS ARE INDICATED. AMEND VERBAGE TO REFLECT THAT | | | THE DEVICES ARE SMOKE ALARMS. PLEASE BE ADVISED THAT | | | SMOKE DETECTORS ARE TIED INTO A FIRE ALARM SYSTEM, | | | WHEREAS SMOKE ALARMS ALERT THE OCCUPANT(S) OF THE | | | DWELLING UNIT AND IS NOT TIED INTO A FIRE ALARM SYSTEM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|