| Plan Review Notes For Permit 09040215 |
| Permit Number |
09040215 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-16 09:43:17 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. | | | | | | 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | 3} NOTE: THE ROOM LABELS ON THE SECOND FLOOR SHEET | | | E1.0.1 ARE MARKED WITH 1ST AND 2ND FLOOR NUMBERS, | | | PLEASE CORRECT ON PERMIT SET.106.1.1 FBC AS AMENDED. | | | | | | 4} NOTE: THE EMERGENCY LIGHTS MUST NOT BE WIRED TO THE | | | TIME CLOCK (IE: HP 1&2) BUT MUST COMPLY WITH | | | 700.12(F)(4), 2005 NEC. | | | | | | 5} PROVIDE MECHANICAL PLANS AND UNIT SPECIFICATIONS FOR | | | A/C EQUIPMENT SO THAT LOADS AND CIRCUIT SIZING CAN BE | | | REVIEWED ON THE SCHEDULES AND CALCULATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|