2009-05-15 15:17:54REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. NOT ADDRESSED. NO MANUFACTURER'S DATA WAS PROVIDED
 REGARDING THE WIND RESISTANCE CAPABILITIES OF THE
 EXHAUST FAN OR CURB. SHOW COMPLIANCE WIHT FBC-M 301.12.
  
 3. NOT ADDRESSED. FAN STILL APPEARS TO BE LESS THAN 10
 FEET FROM THE ROOF EDGE. GUARDS ARE REQUIRED AT THIS
 LOCATION IN ACCORDANCE WITH FBC-M 304.10.
  
 4. NOT ADDRESSED. FIRE WRAP IS SHOWN ON THE DUCT, BUT
 THE CLEARANCE REQUIREMENTS ALSO APPLY TO THE HOOD. SHOW
 COMPLIANCE WITH FBC-M 506.3.1.2.
  
 5. NOT ADDRESSED.NO INFORMATION IS PROVIDED REGARDING
 THE SCOPE OF WORK RELATED TO PROVISIONS FOR MAKEUP AIR.
 SHOW HOW MAKEUP AIR IS TO BE PROVIDED AS PART OF THE
 SCOPE OF THIS PERMIT OR PROVIDE SEPARATE PERMIT
 APPLICATION. SHOW COMPLIANCE WITH FBC-M 308.1.
  
 6. OK
  
 7. PARTIALLY ADDRESSED, PLAN DOES NOT INDICATE WHAT
 TYPE OF WALL FINISH IS TO BE USED ADJACENT TO THE HOOD.
 PLEASE CLARIFY AND SHOW COMPLIANCE WITH FBC-M 507.9.
  
 8. NOT ADDRESSED. PLEASE CONFIRM VALUATION AS STATED ON
 PERMIT APPLICATION. INCLUDE ALL RELATED WORK. SEE
 PREVIOUS COMMENT. FBC-B 108.3.
  