2009-04-22 13:04:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE UPDATE PLANS TO REFERENCE THE CORRECT CODE
 EDITION. THE 2007 FLORIDA BUILDING CODE WITH 2009
 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009. ALSO, TWO
 OF THE REFERENCED CODE SECTIONS ON SHEET 1 COULD NOT BE
 FOUND IN THE CODE AND DO NOT APPEAR TO EXIST. PLEASE
 REFERENCE CORRECT CODE SECTIONS.
  
 2. PROVIDE MANUFACTURER'S DATA SHOWING THE EXHAUST FAN
 IS DESIGNED FOR WIND RESISTANCE. MECHANICAL APPLIANCES
 AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND PRESSURES AS
 DETERMINED IN ACCORDANCE WITH FBC-M 301.12.
  
 3. BASED ON THE SIDE VIEW ON SHEET 1, THE EXHAUST FAN
 APPEARS TO BE LESS THAN 10 FEET FROM THE ROOF EDGE.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES SUCH AS FANS
 OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED
 WITHIN 10 FEET OF THE ROOF EDGE IN ACCORDANCE WITH
 FBC-M 304.10. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES BEYOND EACH END OF SUCH APPLIANCES AND THE TOP
 OF THE GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES
 ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO COMPLY WITH THE
 REQUIREMENTS FOR GUARDS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4. BASED ON THE SIDE VIEW ON SHEET 1, THERE IS AN A/C
 SUPPLY DUCT IN CLOSE PROXIMITY TO THE NEW HOOD. DUCTS
 AND INSULATION INSTALLED WITHIN 18 INCHES OF A TYPE I
 HOOD SHALL BE NONCOMBUSTIBLE OR SHALL BE LISTED FOR THE
 APPLICATION IN ACORDANCE WITH FBC-M 506.3.1.2.
  
 5. NOTE ON SHEET 1 INDICATES THAT MAKEUP AIR IS TO BE
 PROVIDED BY A/C CONTRACTOR. THERE IS NO SCOPE OF WORK
 RELATED TO THIS WORK ASSOCIATED WITH THIS PERMIT. THE
 SUPPLY OF MAKEUP AIR IS AN INTEGRAL PART OF THE
 CMMERCIAL KITCHEN VENTILATION SYSTEM AND MUST BE DONE
 IN CONJUNCTION WITH THE INSTALLATION OF THE COMERCIAL
 KITCHEN EXHAUST SYSTEM IN ORDER TO PROVIDE A CODE
 COMPLIANT DESIGN IN ACCORDANCE WITH FBC-M 508.1. PLEASE
 EXPAND THE SCOPE OF THIS PERMIT TO INCLUDE MAKEUP AIR
 PROVISIONS OR PROVIDE SEPARATE PLANS AND PERMIT
 APPLICATION FOR THAT SCOPE OF WORK PRIOR TO ISSUANCE OF
 THIS PERMIT.
  
 6. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED
 TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER
 COOKING OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M
 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN SHALL
 OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES,
 BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED
 METHODS. SHOW HOW AUTOMATIC OPERATION OF THE EXHAUST
 SYSTEM WILL BE ACHIEVED.
  
 7. SHEET 1 INDICATES A GYPSUM WALLBOARD FINISH ON THE
 WALL ADJACENT TO THE PROPOSED HOOD. CLEARANCE SHALL NOT
 BE REQUIRED FROM GYPSUM WALLBOARD PROVIDED THAT A
 SMOOTH, CLEANABLE, NONABSORBENT AND NONCOMBUSTIBLE
 MATERIAL IS INSTALLED BETWEEN THE HOOD AND THE GYPSUM
 WALLBOARD OVER AN AREA EXTENDING NOT LESS THAN 18
 INCHES IN ALL DIRECTIONS FROM THE HOOD IN ACCORDANCE
 WITH THE EXCEPTION UNDER FBC-M 507.9.
  
 8. PLEASE CONFIRM VALUATION AS STATED ON PERMIT
 APPLICATION. THE STATED VALUE ON PERMIT APPLICATION IS
 TO INCLUDE ALL LABOR, MATERIAL AND DESIGN COSTS
 ASSOCIATED WITH THE PROPOSED SCOPE OF WORK AT FAIR
 MARKET VALUE, INCLUDING THE PROPOSED ROOFING WORK IN
 ACCORDANCE WITH FBC-B 108.3.
  
 NOTE: SEPARATE ELECTRICAL PERMIT IS REQUIRED FOR POWER
 SUPPLIED TO THIS KITCHEN EXHAUST AND SUPPRESSION
 SYSTEM.
  