| 2009-07-24 18:40:58 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SUBMIT MANUFACTURES SPECS FOR ONE |
| | PRODUCT FOR ATS. THERE IS SUBMITTALS FOR CATERPILLAR |
| | EQUIPMENT AND ALSO LAKE SHORE. WHICH ONE WILL BE USED? |
| | 110.3,90.7 |
| | |
| | 2) NOTE: THE SUBMITTED SP-1 AND RP-1 SHEETS ARE NOT |
| | SIGNED DATED OR SEALED BY THE RESPONSIBLE DESIGNER OF |
| | RECORD. SEE COMMENTS FROM OTHER TRADES |
| | FS 481.221 |
| | |
| | 3) NOTE: THE SUBMITTED LP-1 THROUGH LP-4 CONTAINED |
| | RAISED SEALS OVER PHOTO-COPIED SIGNATURES. THIS DOES |
| | NOT MEET THE MINIMUM UNDER FLORIDA STATUTES 481.221. |
| | ALL COPIES IN BOTH SETS SHALL BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | 4) NOTE: PLANS SUBMITTED DO NOT CONTAIN ANY STRUCTURAL |
| | DETAILS FOR SLAB. SEE COMMENTS FROM BUILDING REVIEW |
| | WITH RESPECT TO NO INFORMATION FOR SLAB, STAIRS AND |
| | PLATFORM. |
| | |
| | 5) NOTE: RISER INDICATES GROUND FAULT PROTECTION ON THE |
| | 800AMP BREAKER ON GENERATOR?? PLEASE HAVE ENGINEER CALL |
| | TO GO OVER THIS AS HAVING *GROUND FAULT PROTECTION* |
| | WILL CREATE A LACK OF COORDINATION FOR GENERATOR BACK |
| | UP. THIS IS NOT THE SAME AS GROUND FAULT SENSING AND |
| | THE COORDINATION OF POWER TRANSFER BACK TO NORMAL |
| | POWER. |
| | |
| | |
| | |
| | ** EMAIL WAS SENT TO OFFICE OF ENGINEER TO CALL AND GO |
| | OVER PLANS SPECIFIC TO COMMENT #4. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |