| 2009-08-04 07:44:33 | BUILDING PLAN REVIEW |
| | PERMIT: 09040174 |
| | ADD: 1590 FLORIDA MANGO |
| | CONT: SOUTH EAST CERTIFIED CONTRACTORS |
| | TEL: (561)635-6935 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | AUGUST 4 /09 |
| | BUILDING PROVISO |
| | SHOP DRAWING TO BE REVIEWED BY DESIGN PROFESSIONAL |
| | BEFORE THE SUBMITTAL TO CITY FOR REVIEW BEFORE |
| | INSPECTION. |
| | NFPA 110: 8.4 OPERATIONAL INSPECTION AND TESTING. |
| | 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS, |
| | SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT |
| | LEAST MONTHLY. |
| | |
| | 1) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT |
| | ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF |
| | THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO |
| | NOT SERVE MORE THAN 20 PEOPLE SHALL BE PERMITTED TO |
| | HAVE A MINIMUM CLEAR WIDTH OF 22 INCHES (559 MM), |
| | MINIMUM TREAD DEPTH OF 10 INCHES (254 MM), MAXIMUM |
| | RISER HEIGHT OF 9 INCHES (229 MM), MINIMUM |
| | HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM |
| | HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM). |
| | |
| | 2) GAURDRAILS: 1012.1 WHERE REQUIRED. |
| | GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING |
| | SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS |
| | WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE |
| | THE FLOOR OR GRADE BELOW. |
| | GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN |
| | ACCORDANCE WITH SECTION 1607.7. |
| | |
| | 3) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS: |
| | 2.AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE OF |
| | ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR |
| | EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID |
| | MATERIALS SUCH THAT A |
| | SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT |
| | PASS THROUGH ANY OPENING. |
| | 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN |
| | OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS, |
| | HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION |
| | SHALL NOT PERMIT A SPHERE WITH A |
| | DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY |
| | OPENING. |
| | |
| | 4) BEFORE A CERTIFICATE OF COMPLETION CAN BE ISSUED |
| | PLEASE PROVIDE EVIDENCE THAT THE TOP OF THE GENERATOR |
| | SLAB IS AT OR ABOVE ELEVATION 13.5' NGVD, FLOOD ZONE |
| | A-9 |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |