2009-07-27 17:39:37BUILDING PLAN REVIEW
 PERMIT: 09040174
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTH EAST CERTIFIED CONTRACTORS
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 27/09
 3RD REVIEW
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) THE PLAN DOES NOT NDICATE IF THIS IS A NEW SLAB OR
 REUSE OF AN EXISTING SLAB. 2702.1.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE NFPA 70, NATIONAL ELECTRICAL
 CODE, NFPA 110 AND NFPA 111.
 NFPA 110:
 3A) 7.4 MOUNTING.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE
 UNIT DURING OPERATION. PLANS DO NOT PROVIDE INFORMATION
 FOR SECONDARY CONTAINMENT. NFPA 110: 7.9.12 LISTED
 GENERATOR SUBBASE SECONDARY CONTAINMENT FUEL TANKS OF
 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING.PLANS DO NOT INDICATE THE GALLON CAPACITY.
  
 4) PLANS FAIL TO PROVIDE INFORMATION FOR THE FOUNDATION
 AND SLAB FOR GENERATOR A TANK, PLEASE PROVIDE DETAILS
 FOR ANCHORING OF TANK AND GENERATOR AGAINST OVERTURNING
 ,UPLIFT AND SLIPPAGE FBC BUILDING 1609.1.3
  
 5) COMMENT NUMBER 5 DEALS WWITH THE REASON A STAIR AND
 ACCESS PLATFORM IS REQUIRED. FOR MAINTENANCE AND WEEKLY
 VISUAL INSPECTION OF GENERATOR A ELEVATED PLATFORM,
 STAIR AND GUARDRAIL SYSTEM WILL BE REQUIRED. NFPA 110:
 8.4 OPERATIONAL INSPECTION AND TESTING. 8.4.1* EPSSS,
 INCLUDING ALL APPURTENANT COMPONENTS, SHALL BE
 INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT LEAST
 MONTHLY. DEPENDING ON TTHE HEIGHT OF THE FUEL TANK.
  
 6)PLEASE PROVIDE CODE COMPLIANCE. STAIRS 1009.3
 EXCEPTION# 7. INDUSTRIAL EQUIPMENT ACCESS STAIRS AND
 LANDINGS THAT SERVE AS A COMPONENT OF THE MEANS OF
 EGRESS FROM THE INVOLVED EQUIPMENT AND DO NOT SERVE
 MORE THAN 20 PEOPLE SHALL BE PERMITTED TO HAVE A
 MINIMUM CLEAR WIDTH OF 22 INCHES (559 MM), MINIMUM
 TREAD DEPTH OF 10 INCHES (254 MM), MAXIMUM RISER HEIGHT
 OF 9 INCHES (229 MM), MINIMUM HEADROOM OF 6 FEET 8
 INCHES (2032 MM), AND A MAXIMUM HEIGHT BETWEEN LANDINGS
 OF 12 FEET (36 576 MM).
  
 7) PLEASE PROVIDE CODE COMPLIANCE. GAURDRAILS: 1012.1
 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 8)PLEASE GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3. IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 9) THE FLOOR PLAN DOES NOT INDICATE THIS GENERATOR
 BEING LOCATED IN A SEPERATE GENERATOR ROOM.
 NFPA 110 .7.2.1.2
 NFPA 110. 7.2.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved