| Date |
Text |
| 2009-07-05 16:11:11 | |
| | |
| | |
| | |
| | |
| | |
| | ** DENIED 2ND PLANS REVIEW ** |
| | |
| | 1) NOTE: THIS COMMENT WAS IGNORED: PERMIT APPLICATION |
| | VALUE SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT, |
| | DESIGN COST ETC. AN APPLIED VALUE OF $12K DOES NOT |
| | COVER THE GENERATOR LET ALONE THE TRANSFER EQUIPMENT, |
| | SLAB WORK, ELECTRICAL, UNDERGROUND OR FUEL TANK. |
| | IF AN APPROPRIATE VALUE IS NOT STATED FOR COMPLETE |
| | SCOPE ONE WILL BE ASSESSED USING THE ADOPTED GUIDES FOR |
| | VALUE AND INCLUDING PRICING PROVIDED FROM MANUFACTURES. |
| | FBC 108.3 |
| | |
| | 2) NOTE: THIS COMMENT REMAINS AS THERE IS NOT ENOUGH |
| | INFORMATION FOR OTHER TRADES WHICH WILL CREATE 2ND |
| | ROUND OF COMMENTS FOR OTHER REVIEWS AS WELL. |
| | **PLEASE BE SURE TO SEE ALL COMMENTS FROM OTHER TRADES |
| | AS THERE WILL BE COMMENTS WITH RESPECT TO FUEL SIZE AND |
| | THE REQUIREMENT FOR AN ACCESS PLATFORM TO SERVICE |
| | EQUIPMENT PER NFPA-110 2002 AND FBC. |
| | THERE WILL BE COMMENTS WITH RESPECT TO MOUNTING, AND |
| | THE ACTUAL FUEL TANK PLANS NEEDING THE DERM STAMPS. |
| | ** THIS IS NOTED SO THAT DESIGN TEAM AND CONTRACTOR |
| | WILL BE AWARE TO SEE OTHER COMMENTS BEFORE MAKING |
| | DESIGN CHANGES. |
| | |
| | 3) NOTE: REPEAT COMMENT: PLEASE SUBMIT THE MANUFACTURES |
| | SPECS/CUT SHEETS FOR ALL EQUIPMENT. THIS SHALL INCLUDE |
| | ATS EQUIPMENT, GENERATOR, AND FUEL TANK. (TANK REVIEWED |
| | BY OTHER TRADES). |
| | NEC 90.7,110.3, 702.6 |
| | |
| | 4) NOTE: SAME NOTE, THE ATS IS STILL SHOWN AS 3-POLE. |
| | THERE WILL BE A LACK OF COORDINATION OF EQUIPMENT AND |
| | WHEN POWER TRANSFER BACK TO NORMAL POWER. |
| | |
| | **PREVIOUS NOTE: |
| | PLEASE SEE ORIGINAL NOTES FOR BUILDING. THE CODE |
| | REQUIRES GROUND FAULT PROTECTION ON MAIN. THIS IS GIVEN |
| | FOR INFORMATION AS THIS IS ONLY A NEC 702 SYSTEM. |
| | AS THERE IS GROUND FAULT PROTECTION ON THE MAIN AND THE |
| | USE OF A THREE POLE TRANSFER SWITCH THIS MAY CREATE A |
| | LACK OF COORDINATION OR TRIPPING OF MAIN WITHOUT THE |
| | USE OF A FOUR POLE TRANSFER SWITCH. IF THIS WAS A 700 |
| | OR 701 SYSTEM THERE ARE SPECIFIC CODE SECTIONS WHICH |
| | REQUIRE GROUND FAULT SENSING ON THE BACK UP SYSTEM. |
| | PLEASE SEE NFPA-110 6.2.15 WHEN GROUND FAULT SENSING IS |
| | REQUIRED OR PROVIDED THIS WOULD REQUIRE THE ISOLATION |
| | OF NEUTRALS THUS A FOUR POLE TRANSFER SWITCH. |
| | *** PLEASE BE AWARE OF THIS AS THIS MAY BE AN |
| | OPERATIONAL ITEM WHICH DEPENDING ON EQUIPMENT ORDERED |
| | MAY CREATE A LOSS OF COORDINATION OR NO OPERATION AT |
| | ALL. |
| | ** PLEASE SEE WHITE PAPERS BY CATERPILLAR, ASCO AND |
| | MANY OTHER TRANSFER SWITCH MANUFACTURES ON THIS TOPIC. |
| | ** THIS COMMENT IS ONLY MADE TO HELP IN THE DESIGN AS |
| | THIS IS A 702 SYSTEM NO BACK UP OF POWER IS REQUIRED |
| | FOR ANY 701 AND 702 SYSTEMS IN BUILDING. |
| | |
| | 5) NOTE: NEW SITE PLANS ARE IN FACT PHOTO-COPIES OF |
| | SIGNED, DATED AND SEALED PLANS BY A DESIGN PROFESSIONAL |
| | WHICH IS NOT PERMITTED. |
| | FS 481.221, 471.025 |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |