Plan Review Notes
Plan Review Notes For Permit 09040174
Permit Number 09040174
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-05 16:11:11 
  
  
  
  
  
 ** DENIED 2ND PLANS REVIEW **
  
 1) NOTE: THIS COMMENT WAS IGNORED: PERMIT APPLICATION
 VALUE SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST ETC. AN APPLIED VALUE OF $12K DOES NOT
 COVER THE GENERATOR LET ALONE THE TRANSFER EQUIPMENT,
 SLAB WORK, ELECTRICAL, UNDERGROUND OR FUEL TANK.
 IF AN APPROPRIATE VALUE IS NOT STATED FOR COMPLETE
 SCOPE ONE WILL BE ASSESSED USING THE ADOPTED GUIDES FOR
 VALUE AND INCLUDING PRICING PROVIDED FROM MANUFACTURES.
 FBC 108.3
  
 2) NOTE: THIS COMMENT REMAINS AS THERE IS NOT ENOUGH
 INFORMATION FOR OTHER TRADES WHICH WILL CREATE 2ND
 ROUND OF COMMENTS FOR OTHER REVIEWS AS WELL.
 **PLEASE BE SURE TO SEE ALL COMMENTS FROM OTHER TRADES
 AS THERE WILL BE COMMENTS WITH RESPECT TO FUEL SIZE AND
 THE REQUIREMENT FOR AN ACCESS PLATFORM TO SERVICE
 EQUIPMENT PER NFPA-110 2002 AND FBC.
 THERE WILL BE COMMENTS WITH RESPECT TO MOUNTING, AND
 THE ACTUAL FUEL TANK PLANS NEEDING THE DERM STAMPS.
 ** THIS IS NOTED SO THAT DESIGN TEAM AND CONTRACTOR
 WILL BE AWARE TO SEE OTHER COMMENTS BEFORE MAKING
 DESIGN CHANGES.
  
 3) NOTE: REPEAT COMMENT: PLEASE SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS FOR ALL EQUIPMENT. THIS SHALL INCLUDE
 ATS EQUIPMENT, GENERATOR, AND FUEL TANK. (TANK REVIEWED
 BY OTHER TRADES).
 NEC 90.7,110.3, 702.6
  
 4) NOTE: SAME NOTE, THE ATS IS STILL SHOWN AS 3-POLE.
 THERE WILL BE A LACK OF COORDINATION OF EQUIPMENT AND
 WHEN POWER TRANSFER BACK TO NORMAL POWER.
  
 **PREVIOUS NOTE:
 PLEASE SEE ORIGINAL NOTES FOR BUILDING. THE CODE
 REQUIRES GROUND FAULT PROTECTION ON MAIN. THIS IS GIVEN
 FOR INFORMATION AS THIS IS ONLY A NEC 702 SYSTEM.
 AS THERE IS GROUND FAULT PROTECTION ON THE MAIN AND THE
 USE OF A THREE POLE TRANSFER SWITCH THIS MAY CREATE A
 LACK OF COORDINATION OR TRIPPING OF MAIN WITHOUT THE
 USE OF A FOUR POLE TRANSFER SWITCH. IF THIS WAS A 700
 OR 701 SYSTEM THERE ARE SPECIFIC CODE SECTIONS WHICH
 REQUIRE GROUND FAULT SENSING ON THE BACK UP SYSTEM.
 PLEASE SEE NFPA-110 6.2.15 WHEN GROUND FAULT SENSING IS
 REQUIRED OR PROVIDED THIS WOULD REQUIRE THE ISOLATION
 OF NEUTRALS THUS A FOUR POLE TRANSFER SWITCH.
 *** PLEASE BE AWARE OF THIS AS THIS MAY BE AN
 OPERATIONAL ITEM WHICH DEPENDING ON EQUIPMENT ORDERED
 MAY CREATE A LOSS OF COORDINATION OR NO OPERATION AT
 ALL.
 ** PLEASE SEE WHITE PAPERS BY CATERPILLAR, ASCO AND
 MANY OTHER TRANSFER SWITCH MANUFACTURES ON THIS TOPIC.
 ** THIS COMMENT IS ONLY MADE TO HELP IN THE DESIGN AS
 THIS IS A 702 SYSTEM NO BACK UP OF POWER IS REQUIRED
 FOR ANY 701 AND 702 SYSTEMS IN BUILDING.
  
 5) NOTE: NEW SITE PLANS ARE IN FACT PHOTO-COPIES OF
 SIGNED, DATED AND SEALED PLANS BY A DESIGN PROFESSIONAL
 WHICH IS NOT PERMITTED.
 FS 481.221, 471.025
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II