| Plan Review Notes For Permit 09040174 |
| Permit Number |
09040174 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-16 12:36:52 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. NO ADDRESS LISTED ON | | | SHEETS E-1, E-2, AND E-3. | | | | | | 2. UPDATE CODE INFORMATION ON SHEET E-1 TO REFLECT | | | CURRENT EDITIONS OF NFPA 101 (2006) AND NFPA 110 (2005) | | | WHICH ARE TO BE REFERENCED. | | | | | | 3. ARE ANY DEVICES PLANNED TO PREVENT THE GENERATOR | | | FROM RECEIVING MECHANICAL DAMAGE FROM VEHICLES. | | | | | | 4. SHOW/ILLUSTRATE DISTANCE FROM THE GENERATOR/SLAB | | | SETUP TO THE EDGE OF THE ONE WAY ASPHALT DRIVE. | | | | | | 5. SHOW/ILLUSTRATE DISTANCES TO THE NEAREST BUILDING(S) | | | OPENINGS SUCH AS WINDOWS AND DOORS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|