Plan Review Notes
Plan Review Notes For Permit 09040174
Permit Number 09040174
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-12 10:15:02** DENIED**
  
 1) NOTE: PLANS ARE STATING ALL DESIGNS PER 2004 FBC.
 ANY PLANS SUBMITTED FOR PER AFTER MARCH 1ST, 2009 MUST
 BE UNDER THE NEW 2007 FBC WITH 2009 AMENDMENTS.
 THE FAC 69A-60.003 AND 004 HAS ALSO REVISED ADOPTING
 THE NEW NFPA-1 AND NFPA-101
  
 PLEASE BE SURE THE FOLLOWING CODES ARE STATED ON PLANS
 AT A MINIMUM.
 2005 NFPA-70
 2002 NFPA-72
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
  
 2) NOTE: PERMIT APPLICATION VALUE SHALL INCLUDE: ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC. AN
 APPLIED VALUE OF $12K DOES NOT COVER THE GENERATOR LET
 ALONE THE TRANSFER EQUIPMENT, SLAB WORK, ELECTRICAL,
 UNDERGROUND OR FUEL TANK.
 IF AN APPROPRIATE VALUE IS NOT STATED FOR COMPLETE
 SCOPE ONE WILL BE ASSESSED USING THE ADOPTED GUIDES FOR
 VALUE AND INCLUDING PRICING PROVIDED FROM MANUFACTURES.
 FBC 108.3
  
 3) NOTE: PLEASE BE SURE TO SEE ALL COMMENTS FROM OTHER
 TRADES AS THERE WILL BE COMMENTS WITH RESPECT TO FUEL
 SIZE AND THE REQUIREMENT FOR AN ACCESS PLATFORM TO
 SERVICE EQUIPMENT PER NFPA-110 2002 AND FBC.
 THERE WILL BE COMMENTS WITH RESPECT TO MOUNTING, AND
 THE ACTUAL FUEL TANK PLANS NEEDING THE DERM STAMPS.
 ** THIS IS NOTED SO THAT DESIGN TEAM AND CONTRACTOR
 WILL BE AWARE TO SEE OTHER COMMENTS BEFORE MAKING
 DESIGN CHANGES.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT. THIS SHALL INCLUDE ATS
 EQUIPMENT, GENERATOR, AND FUEL TANK. (TANK REVIEWED BY
 OTHER TRADES).
 NEC 90.7,110.3, 702.6
  
 5) NOTE: PLEASE SEE ORIGINAL NOTES FOR BUILDING. THE
 CODE REQUIRES GROUND FAULT PROTECTION ON MAIN. THIS IS
 GIVEN FOR INFORMATION AS THIS IS ONLY A NEC 702 SYSTEM.
 AS THERE IS GROUND FAULT PROTECTION ON THE MAIN AND THE
 USE OF A THREE POLE TRANSFER SWITCH THIS MAY CREATE A
 LACK OF COORDINATION OR TRIPPING OF MAIN WITHOUT THE
 USE OF A FOUR POLE TRANSFER SWITCH. IF THIS WAS A 700
 OR 701 SYSTEM THERE ARE SPECIFIC CODE SECTIONS WHICH
 REQUIRE GROUND FAULT SENSING ON THE BACK UP SYSTEM.
 PLEASE SEE NFPA-110 6.2.15 WHEN GROUND FAULT SENSING IS
 REQUIRED OR PROVIDED THIS WOULD REQUIRE THE ISOLATION
 OF NEUTRALS THUS A FOUR POLE TRANSFER SWITCH.
 *** PLEASE BE AWARE OF THIS AS THIS MAY BE AN
 OPERATIONAL ITEM WHICH DEPENDING ON EQUIPMENT ORDERED
 MAY CREATE A LOSS OF COORDINATION OR NO OPERATION AT
 ALL.
 ** PLEASE SEE WHITE PAPERS BY CATERPILLAR, ASCO AND
 MANY OTHER TRANSFER SWITCH MANUFACTURES ON THIS TOPIC.
 ** THIS COMMENT IS ONLY MADE TO HELP IN THE DESIGN AS
 THIS IS A 702 SYSTEM NO BACK UP OF POWER IS REQUIRED
 FOR ANY 701 AND 702 SYSTEMS IN BUILDING.
  
 6) NOTE: PLEASE SEE 225.31-225.39 FOR THE REQUIRED
 DISCONNECTING MEANS FOR FEEDERS AT THE BUILDING. THIS
 WAS NOTED ON THE ORIGINAL PLANS HOWEVER THE GENERATOR
 WAS REMOVED FORM PLANS. THIS REVIEWER STATED TO BE
 AWARE OF THIS CODE SECTION ON FUTURE PLANS. NEC
 700.12B6, 701.11B5 AND 702.11 ALL STATE THAT WHEN
 DISCONNECTING MEANS FROM THE GENERATOR IS LOCATED
 WITHIN SIGHT AND READILY ACCESSIBLE THEN AN ADDITIONAL
 DISCONNECTING MEANS IS NOT REQUIRED AT THE BUILDING IN
 WHICH THE FEEDERS SERVE. THE GENERATOR IS LOCATED
 WITHIN SIGHT PER DEFINITIONS HOWEVER THE DISCONNECTING
 MEANS AT GENERATOR MAY NOT BE READILY ACCESSIBLE. IN A
 LOCKED ENCLOSURE OR BEHIND A WALL/GATES LOCKED DOES NOT
 PERMIT READY ACCESS FOR FIRE DEPARTMENT OR ANY OTHER
 PERSONNEL. SEE ZONING COMMENTS AS THE GENERATOR WILL BE
 REQUIRED TO CONTAIN A WALL OR FENCE IN ETC. THE
 ENCLOSURE OF THE GENERATOR ALONE DOES NOT PERMIT READY
 ACCESS WITH THE BREAKER LOCKED INSIDE.
 PLEASE KNOW THAT A DISCONNECTING MEANS DOES NOT REQUIRE
 OVER CURRENT PROTECTION WHEN THE OCP IS ALREADY
 PROVIDED BY THE GENERATOR.
  
  
  
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  