Plan Review Notes
Plan Review Notes For Permit 09040169
Permit Number 09040169
Review Stop B
Sequence Number 1
Notes
Date Text
2009-04-09 09:43:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE REVISE THE INSTALLATION SCHEDULE SO THAT THE
 COLUMN "SHUTTER CONNECTION MOUNTING TYPE" CORRELATES
 WITH THE ANCHOR SCHEDULES; IN THIS CASE, C1 THROUGH C3.
  
 2. CONCRETE IS REQUIRED TO BE A MINIMUM OF 3000PSI, SEE
 SHEET 3. PRODE EVIDENCE THAT THE CONCRETE MEETS THIS
 REQUIREMENT; A RESIDENTIAL FLOOR SLAB IS TYPICALLY
 POURED WITH 2500PSI STRENGTH CONCRETE.
  
 3. SUBSTRATE, WHAT IS "CC"? SEE ITEM 2.
  
 4. TWO COMPLETE SETS REQUIRED FOR PERMIT ISSUANCE. ONLY
 ONE INSTALLATION SCHEDULE WAS SUBMITTED.
  
  
  