2009-05-22 16:12:06**TEMPORARY FAILED STATUS. **
  
 1) NOTE: PLANS ARE STAMPED HOWEVER ARE REDLINED FOR THE
 FOLLOWING:
  
 A) PLANS SHOW SMOKE ALARM TOO CLOSE TO FAN. MUST MEET
 NFPA-72 11.8.3.
 B) METER/SERVICE AS SHOWN IS GRANTED PER ANGELA
 JONES-VANN
  
 2) NOTE: IN TEMP FAILED STATUS UNTIL ADDRESSING IS
 CLEARED FOR UNITY OF TITLE AND ADDRESS HAS BEEN
 UPDATED.
 ONCE ADDRESS IS CONFIRMED WITH CORRECT UNITY OF TITLE
 ETC BEING RECORDED THEN REVIEW STATUS WILL BE ADJUSTED
 TO *P*. PLANS ARE ALREADY STAMPED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  