Plan Review Notes
Plan Review Notes For Permit 09040157
Permit Number 09040157
Review Stop M
Sequence Number 1
Notes
Date Text
2009-04-14 19:07:56REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. CONDENSATE FROM ALL COOLING COILS SHALL BE CONVEYED
 FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF
 DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO A STREET,
 ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A NUISANCE.
 SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-R M1411.3. DRAIN PIPE JOINTS SHALL
 BE SEALED GAS TIGHT AND SHALL TERMINATE OUTSIDE THE
 BUILDING PERIMETER AT A HEIGHT OF AT LEAST 6 INCHES
 ABOVE THE FINISHED GRADE GROUND LEVEL IN ACCORDANCE
 WITH FBC-R F307.1.2. CONDENSATE LINESSHALL DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE STRUCTURE SIDEWALL IN
 ACCORDANCE WIT FBC-R320.7.
  
 2. PORVIDE DETAIL FOR INSTALLATION OF OUTDOOR
 CONDENSING UNITS. MECHANICAL APPLIANCES AND SUPPORTS
 THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING PER
 FBC-R M1307.3.
  
 3. ONCE ADDRESSING AND UNITY-OF-TITLE ISSUES ARE
 RESOLVED, PLEASE PROVIDE THE CORRECT ADDRESS OF THE
 PROPOSED WORK ON EVERY SHEET OF THE PLANS.
  