2009-04-12 13:22:14** DENIED**
  
 1) NOTE: PLANS SUBMITTED STATE 260 PALMETTO LANE
 HOWEVER THE SCOPE OF WORK ON THE PERMIT APPLICATION
 STATES 250 PALMETTO LANE.
 THE INFORMATION FOR PERMITTING AND PLANS HAS BEEN
 FORWARD TO ADDRESSING AND ZONING.
 THIS AREA IS ZONED SF-7 WHICH IS SINGLE FAMILY. PLANS
 SHOW SEPARATE METER FOR THESE DETACHED BUILDINGS WHICH
 NEEDS TO BE CONFIRMED WITH ZONING. THIS IS A SEPARATE
 PROPERTY.
 THE COMMENTS FROM ZONING MAY OR MAY NOT AFFECT
 ELECTRICAL PLANS.
 THE TITLE BLOCKS NEED TO BE CORRECTED FOR ACTUAL
 LOCATION ONCE REVIEWS CONFIRM FINAL ADDRESS.
  
 2) NOTE: ELECTRICAL PANELS MAY NOT BE LOCATED IN
 STORAGE CLOSETS.
 110.26,240.24D
  
 3) NOTE: SMOKE ALARMS REQUIRED PER NFPA-72 11.5.1 SHOWN
 ON PLANS. HOWEVER PLEASE BE SURE ALL DEVICES ARE
 LOCATED IN AREAS AS REQUIRED PER 11.8.3 (SLOPED
 CEILINGS)
  
 4) NOTE: PLEASE SEE 225.31-225.39 FOR DISCONNECTING
 MEANS REQUIRED AT THE DETACHED PAVILION.
  
 5) NOTE: PLEASE SEE 250.32 FOR REQUIRED GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED PAVILION. THE ONLY
 EXCEPTION DEPENDS ON CIRCUITING. BASED ON PANEL
 SCHEDULE, GROUNDING ELECTRODE TO FOOTER STEEL, GROUND
 RODS ARE REQUIRED.250.50
 THIS IS ALSO FOR EACH OF THE CABANA BUILDING AS THERE
 IS NO GROUNDING ELECTRODE SYSTEM AT EITHER STRUCTURE
 WHICH IS REQUIRED.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  