| Date |
Text |
| 2009-04-12 13:22:14 | ** DENIED** |
| | |
| | 1) NOTE: PLANS SUBMITTED STATE 260 PALMETTO LANE |
| | HOWEVER THE SCOPE OF WORK ON THE PERMIT APPLICATION |
| | STATES 250 PALMETTO LANE. |
| | THE INFORMATION FOR PERMITTING AND PLANS HAS BEEN |
| | FORWARD TO ADDRESSING AND ZONING. |
| | THIS AREA IS ZONED SF-7 WHICH IS SINGLE FAMILY. PLANS |
| | SHOW SEPARATE METER FOR THESE DETACHED BUILDINGS WHICH |
| | NEEDS TO BE CONFIRMED WITH ZONING. THIS IS A SEPARATE |
| | PROPERTY. |
| | THE COMMENTS FROM ZONING MAY OR MAY NOT AFFECT |
| | ELECTRICAL PLANS. |
| | THE TITLE BLOCKS NEED TO BE CORRECTED FOR ACTUAL |
| | LOCATION ONCE REVIEWS CONFIRM FINAL ADDRESS. |
| | |
| | 2) NOTE: ELECTRICAL PANELS MAY NOT BE LOCATED IN |
| | STORAGE CLOSETS. |
| | 110.26,240.24D |
| | |
| | 3) NOTE: SMOKE ALARMS REQUIRED PER NFPA-72 11.5.1 SHOWN |
| | ON PLANS. HOWEVER PLEASE BE SURE ALL DEVICES ARE |
| | LOCATED IN AREAS AS REQUIRED PER 11.8.3 (SLOPED |
| | CEILINGS) |
| | |
| | 4) NOTE: PLEASE SEE 225.31-225.39 FOR DISCONNECTING |
| | MEANS REQUIRED AT THE DETACHED PAVILION. |
| | |
| | 5) NOTE: PLEASE SEE 250.32 FOR REQUIRED GROUNDING |
| | ELECTRODE SYSTEM AT THE DETACHED PAVILION. THE ONLY |
| | EXCEPTION DEPENDS ON CIRCUITING. BASED ON PANEL |
| | SCHEDULE, GROUNDING ELECTRODE TO FOOTER STEEL, GROUND |
| | RODS ARE REQUIRED.250.50 |
| | THIS IS ALSO FOR EACH OF THE CABANA BUILDING AS THERE |
| | IS NO GROUNDING ELECTRODE SYSTEM AT EITHER STRUCTURE |
| | WHICH IS REQUIRED. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |