| Plan Review Notes For Permit 09040157 |
| Permit Number |
09040157 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-13 19:10:23 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008 | | | REVISIONS. | | | | | | 1- PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG | | | RD (233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING | | | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE | | | DUE. | | | | | | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR BATH EXTERIOR DOOR. | | | | | | 3- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | APPROVED IN WRITING (NOT SIGNING AND SEALING) AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | | | 4- PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR | | | ICYNENE INSULATION TO VERIFY COMPLIANCE WITH SEC. R314 | | | AND R316 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 5- SHEET S-1: PAVILION ROOF FRAMING PLAN IS MISSING THE | | | ROOF CONNECTOR FOR 2X8 RAFTERS ON CANTILEVER SIDE. THIS | | | INFORMATION IS MISSING ALSO ON DETAIL 1/S-2. | | | | | | 6- SHEET S-3; REVISE WIND LOAD INFORMATION. EDGE | | | DISTANCE TO BE 4'-0" MIN. AS REQUIRED BY FIGURE | | | R301.2(7) OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 7- SHEET A-2: SPECIFY FIREBLOCKING MATERIAL AND | | | LOCATION ON TYPICAL WALL SECTIONS A AND B AS REQUIRED | | | BY SEC. R602.1.2 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 8- OWES $9.88 FOR RADON FEES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|