| 2009-04-20 11:27:29 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. GOVERNING CODE IS FBC2007 WITH 2009 SUPPLEMENTS |
| | EFFECTIVE MARCH 1, 2009. PLEASE REVISE. |
| | |
| | 2. IMPACT FEES MAY BE DUE. PLEASE CONTACT 561-233-5025. |
| | PLANS MUST BE STAMPED AND THE RECEIPT (IF FEES ARE DUE) |
| | TO BE ATTACHED TO THE APPLICATION. |
| | |
| | 3. ENERGY CALC 2007 FORM REQUIRED, SEE COMMENT 1. |
| | |
| | 4. PLEASE CLARIFY; FBC13 FORM 600 C, THIS FORM APPLIES |
| | ONLY TO COMPONENTS BEING INSTALLED. .3 IS SHOWN FOR |
| | SLAB; IS A SLAB TO BE INSTALLED? THIS COMMENT WAS ON |
| | THE PREVIOUS CORRECTION LIST 08070697. PLEASE CHECK ALL |
| | INFORMATION ON THE ENERGY CALC AND INCLUDE ONLY |
| | COMPONENTS TO BE INSTALLED. |
| | |
| | 5. DESIGN LOADS SHOWN ON DESIGN PARAMETERS BOX DO NOT |
| | MATCH DESIGN LOADS SHOWN ON STRUCTURAL NOTE 2A. PLEASE |
| | REVISE. |
| | |
| | 6. STRUCTURAL NOTE 14 STATES THAT A 1/2" EXT PLYWOOD |
| | VENT IS REQUIRED, PLEASE CLARIFY, WHAT DOES THIS MEAN? |
| | |
| | 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | TH FRENCH DOORS, SINGLE HUNG WINDOWS, IMPACT |
| | PROTECTION, FAC9B72. |
| | |
| | 8. IF SHUTTERS ARE USED AS IMPACT PROTECTION, SUBMIT |
| | AND INSTALLATION SCHEDULE TO PROVIDE INFORMATION |
| | REGARDING PROPOSED INSTALLATION METHODS TO SHOW |
| | COMPLIANCE WITH FBC R301. THIS FORM CAN BE LOCATED IN |
| | THE LOBBY OR AT HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/P |
| | DF/SCHEDULE_FOR_INSTALLATION.PDF. |
| | |
| | 9. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD FBC*106.3.3. |
| | |
| | 10. INCORRECT ASCE 7 REFERENCE, SEE FBC R43. |
| | |
| | |
| | |