2009-04-13 11:40:35GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2007 FLORIDA BUILDING CODES, CITY
 OF WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.),
 FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA
 STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE REFERENCED CODE N.F.G.C. IS INCORRECT.
 FBC FUEL GAS 2007 IS REQUIRED. TABLES 402.4(2) AND
 402.4(19) APPLY.
  
 2. FROM TABLE 402.4(19) 1" PIPE SIZE IS REQUIRED FOR
 THE POOL HEATER.
  
 REVIEW BY LARRY WAGNER