| Plan Review Notes For Permit 09040094 |
| Permit Number |
09040094 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-06-04 14:01:17 | MET WITH THE HOMEOWNER AT THE RESIDENCE TO VERIFY CODE | | | COMPLIANCE WITH THE 2007 FEBC AND FOR THE REQUESTED | | | CHANGE OF OCCUPANCY. THE FOLLOWING WAS OBSERVED: | | | | | | 1) THE CARE INDICATED ON THE PLAN IS FOR 6 ADULTS FOR | | | 24 HOUR SUPERVISION. | | | 2) AS PER THE FBC, SECTION 308.2 THE INTENDED OCCUPANCY | | | SHALL BE CLASSIFIED AS R-4. THE EXISTING OCCUPANCY IS | | | R-3. | | | 3) AS PER SECTION 912 .4, FEBC, ALL MEANS OF EGRESS | | | SHALL COMPLY WITH CHAPTER 10 OF THE FBC. THE BEDROOM ON | | | LOCATED ON THE 2ND FLOOR, WEST ELEVATION DOES NOT | | | POSSESS AN EMERGENCY ESCAPE/RESCUE OPENING AND, | | | THEREFORE,,DOES NOT MEET THE REQUIREMENTS OF THE | | | FORMER. | | | 4) ACCESSIBILITY: ALL BUIDINGS UNDERGOING A CHANGE OF | | | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION | | | 912.8. THE BATHROOM DOOR SHALL HAVE A 29" CLEARANCE. | | | 5) FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN | | | ACCORDANCE WITH SECTIONS 912.2.1 AND 912.2.2 OF THE | | | FEBC. | | | 6.) THE EXISTING STAIR HANDRAIL HEIGHT REQUIRES | | | ADJUSTMENT AS PER SECTION 912.4.1. |
|