| Plan Review Notes For Permit 09040094 |
| Permit Number |
09040094 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-05 13:29:28 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 101, 2006 EDITION. | | | | | | 2) PLEASE PROVIDE A MINIMUM OF TWO (2) COPIES OF FLOOR | | | PLANS AND ALL SUPPORTING DOCUMENTS FOR REVIEW. | | | | | | 3) PLEASE VERIFY THE NUMBER OF RESIDENTS AND THEIR | | | ABILITY AS A GROUP TO MOVE RELIABILY TO A POINT OF | | | SAFETY WITHIN (3) MINUTES. 101. SEC. 32.2.3.5.2. | | | | | | 4) APPROVED SMOKE ALARMS SHALL BE PROVIDED AND | | | INSTALLED ON ALL LEVELS, LIVING AREAS AND INSIDE OF | | | EACH BEDROOM AND SHALL BE INTERCONNECTED SO THE | | | ACTIVATION OF ONE ALARM SHALL CAUSE ALL THE ALARMS TO | | | SOUND. | | | | | | 5) THE EXISTING FIRE ALARM SYSTEM TO BE INSPECTED AND | | | TAGGED BY A CERTIFIED FIRE ALARM CONTRACTOR. THE SYSTEM | | | WILL REQUIRE A FUNCTION TEST IF IT HAS BEEN OUT OF | | | SERVICE. | | | | | | 6) AN EXIT IS ILLUSTRATED FROM THE FAMILY ROOM THROUGH | | | A CAR PORT. WHAT WILL PREVENT PARKED VEHICLES FROM | | | CAUSING AN OBSTRUCTION DURING EMERGENCY EXITING | | | ACTIVITIES? | | | | | | 7) IF NOT ALREADY PROVIDED, THE BEDROOM DOORS SHALL BE | | | 1 3/4" SOLID BONDED WOOD CORE CONSTRUCTION. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|