| 2009-04-13 16:40:47 | ** DENIED** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM |
| | CODES ARE STATED ON PLANS. |
| | 2007 FBC W/ 2009 REVISIONS. |
| | 2006 NFPA-101 |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | |
| | 2) NOTE: THE PLANS SUBMITTED WITH PROJECT BY INTEGRATED |
| | SECURITY SYSTEMS HAVE THE FOLLOWING TWO COMMENTS: |
| | |
| | A) NOTE: TITLE BLOCK FOR ENGINEERING FIRM IS MISSING |
| | THE REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER PER FS |
| | 471.023 AND FAC 61G15-23.002 |
| | |
| | B) NOTE: PLANS NOTING ADA COMPLIANCE PER 1992 ADA |
| | GUIDELINES. |
| | |
| | C) PLANS NOTING CODES WHICH ARE NO LONGER IN EFFECT. |
| | EXAMPLE: PLANS SHOW THE 2002 NEC.( NFPA70) HOWEVER THE |
| | STATE OF FLORIDA ADOPTED THE 2005 NEC IN DECEMBER 2006 |
| | EXAMPLE: PLANS NOTE THE 2003 NFPA-101. FAC 69A-60.003 |
| | AND .004 HAS ADOPTED THE NEW 2006 NFPA-101 AND NFPA-1 |
| | AS OF DECEMBER 31ST, 2008. |
| | |
| | ** PLEASE ADJUST NOTES AND PLANS. |
| | |
| | 3) NOTE: PLANS SUBMITTED CONTAIN THE LIGHTING |
| | PERFORMANCE CALCULATIONS, ALLOWANCES AND CODE SECTIONS |
| | FROM THE 2004 FBC CHAPTER 13. PLEASE KNOW THIS PROJECT |
| | IS UNDER THE 2007 FBC AND THE NEW SECTIONS AND CODE |
| | REQUIREMENT OF 2007 FBC WITH 2009 REVISION APPLY. |
| | THE PREVIOUS CODE ALLOWANCES FOR ACCENT LIGHTING NO |
| | LONGER EXISTS IN THE NEW CODE. |
| | PLANS STATING ANY PRESCRIPTIVE *C* REQUIREMENTS IS NOT |
| | ACCURATE AS THAT SECTION OF THE CODE NO LONGER EXISTS. |
| | |
| | *** IMPORTANT; EMERGENCY LIGHTING WHICH IS ALSO USED |
| | AND GENERAL LIGHTING IS NOT EXEMPT. THE ONLY TYPE OF |
| | EMERGENCY FIXTURES WHICH ARE EXEMPT IS THE BATTERY BACK |
| | UP TYPES ONLY ON UNDER EMERGENCY CONDITIONS. |
| | ** THE LIGHTING SHOWN ON PLANS EXCEEDS THE ALLOWANCES |
| | BY THE CODE. |
| | |
| | *** CALLED FAE CONSULTING ENGINEERS AND SPOKE TO MIKE. |
| | THEY ARE NOW AWARE OF THE NEW CODE REQUIREMENTS AND |
| | WILL BE MAKING CORRECTIONS. |
| | |
| | 4) NOTE: TRANSFORMER HANDING DETAIL NEEDED FOR |
| | STRUCTURAL INTEGRITY. FBC 1606.2 WILL BE PART OF |
| | STRUCTURAL REVIEW. |
| | |
| | 5) NOTE: NOTES ON PLANS INDICATE OVER RIDES FOR |
| | LIGHTING TO SOME SORT OF TIME CLOCK HOWEVER THERE ARE |
| | NO DETAILS ON PLANS FOR PROPOSED LIGHTING CONTROLS. |
| | 13-415.1.AB.1.1, .1.2, .1.3 |
| | |
| | 6) NOTE: NOTES REQUIRED ON PLANS PER 13-413.AB.2 |
| | |
| | 7) NOTE: PLEASE PLACE NOTE ON PLANS FOR ROOM 901 WHICH |
| | STATES WIRING METHODS PERMITTED IN NEC 645 SHALL NOT BE |
| | USED. THIS ROOM DOES NOT MEET REQUIREMENTS IN 645.4 |
| | (1-5) FOR THE LESS STRINGENT WIRING METHODS IN 645. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |