| 2009-05-11 14:51:26 | BUILDING PLAN REVIEW | | | PERMIT: 09040031 | | | ADD: 401 N DIXIE HWY | | | CONT: M. A. C. CONSTRUCTION, INC. | | | TEL: (786)236-1006 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | | | | 1) SHEET M-601 DETAIL SUPPLY FAN ROOF CURB DETAIL, | | | NOTE# 12 SECURE ROOF CURB TO ROOF ASSEMBLY PER | | | MANUFACTURERS INSTALATION INSTRUCTIONS AND STRUCTURAL | | | NOTES. | | | PLEASE PROVIDE TYPE OF ROOF-DECK, AND THE CONNECTION | | | BETWEEN THE ROOF FRAMING, ROOF DECK AND CURBING. | | | THE CITY IS LOCATED WITHIN A 140 M. P.H. 3SECOND GUST | | | WIND ZONE.FIGURE 1609. | | | | | | 1604.8.1 GENERAL. ANCHORAGE OF THE ROOF TO WALLS AND | | | COLUMNS, AND OF WALLS AND COLUMNS TO FOUNDATIONS, SHALL | | | BE PROVIDED TO RESIST THE UPLIFT AND SLIDING FORCES | | | THAT RESULT FROM THE APPLICATION OF THE PRESCRIBED | | | LOADS. | | | | | | 1604.4 ANALYSIS. EVERY STRUCTURE SHALL BE DESIGNED TO | | | RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL | | | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR | | | WIND LOADS . | | | PLEASE PROVIDE BY ROUGH INSPECTION. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | |
|