| Plan Review Notes For Permit 09040031 |
| Permit Number |
09040031 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-13 15:23:46 | ** DENIED | | | | | | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM | | | CODES ARE STATED ON PLANS. | | | 2007 FBC W/ 2009 REVISIONS. | | | 2006 NFPA-101 | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | | | | ** PLANS HAVE OLDER CODES ON THEM | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE ROOFTOP GFI | | | RECEPTACLES PER 210.63, 210.8B3, PLEASE SHOW | | | CIRCUITING. | | | | | | ** THESE ITEMS ARE ITEMS WHICH COULD HAVE BEEN REDLINED | | | HOWEVER PLANS WILL MOST LIKELY HAVE COMMENTS FROM OTHER | | | TRADES SUCH AS MECHANICAL FOR ROOF-TOP EQUIPMENT. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|