| Plan Review Notes For Permit 09040022 |
| Permit Number |
09040022 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-07-04 10:22:33 | ** REDLINED PLANS** | | | | | | 1) NOTE: LOAD CALCULATIONS INDICATE TWO ELECTRICAL | | | WATER HEATERS YET THE PLANS AND THE PANEL SCHEDULE ONLY | | | INDICATE ONE UNIT. PER 422.13 THE LOAD FOR WATER | | | HEATERS ARE TO BE SHOWN AT 125%. HOWEVER SINCE THERE IS | | | AN EXTRA WATER HEATER FIGURED WHEN NOT INSTALLED LOAD | | | IS OK> | | | | | | 2) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES. THE | | | WATER HEATER IN LAUNDRY ROOM IS SHOWN IN THE MINIMUM | | | WORKING SPACE REQUIRED FOR ELECTRICAL PANEL. THIS NEEDS | | | TO MEET SECTION AS THIS IS A LIFE SAFETY HAZARD. PLEASE | | | RELOCATE WATER HEATER OR ADJUST LOCATION TO MEET | | | MINIMUM. | | | | | | ** THE ABOVE COMMENTS ALONG WITH ANY OTHER CHANGES | | | DURING THE ROUGH IN PROCESS NEED TO BE REVISED BEFORE | | | ROUGH ELECTRICAL INSPECTION. IF THERE ARE ANY QUESTIONS | | | ON THE PROCESS OR WHAT NEEDS TO BE REVISED, PLEASE | | | CALL. | | | **IF REAR OPEN AREA IS REVISED TO CLOSE IN AS PART OF | | | THE HOUSE, THE SERVICE WILL BE REQUIRED TO BE | | | RELOCATED. MAY NOT HAVE THE SERVICE/ METER LOCATED | | | INSIDE THE HABITABLE SPACE INSIDE DWELLING AREA. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|