Plan Review Notes
Plan Review Notes For Permit 09040022
Permit Number 09040022
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-04 10:22:33** REDLINED PLANS**
  
 1) NOTE: LOAD CALCULATIONS INDICATE TWO ELECTRICAL
 WATER HEATERS YET THE PLANS AND THE PANEL SCHEDULE ONLY
 INDICATE ONE UNIT. PER 422.13 THE LOAD FOR WATER
 HEATERS ARE TO BE SHOWN AT 125%. HOWEVER SINCE THERE IS
 AN EXTRA WATER HEATER FIGURED WHEN NOT INSTALLED LOAD
 IS OK>
  
 2) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES. THE
 WATER HEATER IN LAUNDRY ROOM IS SHOWN IN THE MINIMUM
 WORKING SPACE REQUIRED FOR ELECTRICAL PANEL. THIS NEEDS
 TO MEET SECTION AS THIS IS A LIFE SAFETY HAZARD. PLEASE
 RELOCATE WATER HEATER OR ADJUST LOCATION TO MEET
 MINIMUM.
  
 ** THE ABOVE COMMENTS ALONG WITH ANY OTHER CHANGES
 DURING THE ROUGH IN PROCESS NEED TO BE REVISED BEFORE
 ROUGH ELECTRICAL INSPECTION. IF THERE ARE ANY QUESTIONS
 ON THE PROCESS OR WHAT NEEDS TO BE REVISED, PLEASE
 CALL.
 **IF REAR OPEN AREA IS REVISED TO CLOSE IN AS PART OF
 THE HOUSE, THE SERVICE WILL BE REQUIRED TO BE
 RELOCATED. MAY NOT HAVE THE SERVICE/ METER LOCATED
 INSIDE THE HABITABLE SPACE INSIDE DWELLING AREA.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  