| 2009-04-10 16:39:11 | ** DENIED** |
| | |
| | 1) NOTE: PLANS ARE STATING ALL DESIGNS PER 2004 FBC. |
| | ANY PLANS SUBMITTED FOR PER AFTER MARCH 1ST, 2009 MUST |
| | BE UNDER THE NEW 2007 FBC WITH 2009 AMENDMENTS. |
| | PLEASE BE SURE THE FOLLOWING CODES ARE STATED ON PLANS |
| | AT A MINIMUM. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2007 FBC RESIDENTIAL |
| | |
| | 2) NOTE: PLANS STATE SMOKE DETECTORS. SMOKE DETECTORS |
| | ARE UNITS WHICH ONLY DETECT AND DO NOT SOUND. PLEASE |
| | SEE DEFINITIONS IN NFPA-72 2002. PLEASE KNOW THAT SMOKE |
| | ALARMS ARE DEVICES WHICH DETECT AND SOUND. IF THESE ARE |
| | INDEED SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH FIRE |
| | ALARM PANEL, SOUNDING DEVICES. |
| | ** PLEASE ALSO SHOW COMPLETE LAYOUT OF EXISTING |
| | DWELLING. ALL EXISTING LOCATIONS MUST BE BROUGHT UP TO |
| | CURRENT NFPA-72 11.5.1 FOR SMOKE ALARMS. |
| | PLEASE SEE FBC R313. |
| | ** PLEASE ALSO SEE 210.12 OF THE NEC AS THIS REQUIRES |
| | ARC FAULT PROTECTION. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR APPLIED SCOPE |
| | OF WORK PER 2005 NEC. |
| | THE NEC 2005 WAS GIVEN IN GENERAL AS THERE ARE MANY |
| | CODE SECTION WHICH NEED TO BE MET ON MINIMUM DESIGN.THE |
| | PERMIT APPLICATION STATES COMPLETE RE-WIRE HOWEVER |
| | PLANS DO NOT SHOW ANY LIGHTING, LIGHTING CONTROLS PER |
| | 210.70. |
| | NO CIRCUITING OR PANEL SCHEDULES PER 408.4 PLEASE BE |
| | SURE ALL REQUIRED CIRCUITING PER 210.52,210.11,220 ARE |
| | SHOWN AND LISTED. |
| | PLEASE SEE 210.52 FOR MISSING RECEPTACLES. |
| | |
| | 4) NOTE: PLEASE BE SURE TO INCLUDE ARC FAULT PROTECTION |
| | 210.12 |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |