Plan Review Notes
Plan Review Notes For Permit 09040022
Permit Number 09040022
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-10 16:39:11** DENIED**
  
 1) NOTE: PLANS ARE STATING ALL DESIGNS PER 2004 FBC.
 ANY PLANS SUBMITTED FOR PER AFTER MARCH 1ST, 2009 MUST
 BE UNDER THE NEW 2007 FBC WITH 2009 AMENDMENTS.
 PLEASE BE SURE THE FOLLOWING CODES ARE STATED ON PLANS
 AT A MINIMUM.
 2005 NFPA-70
 2002 NFPA-72
 2007 FBC RESIDENTIAL
  
 2) NOTE: PLANS STATE SMOKE DETECTORS. SMOKE DETECTORS
 ARE UNITS WHICH ONLY DETECT AND DO NOT SOUND. PLEASE
 SEE DEFINITIONS IN NFPA-72 2002. PLEASE KNOW THAT SMOKE
 ALARMS ARE DEVICES WHICH DETECT AND SOUND. IF THESE ARE
 INDEED SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH FIRE
 ALARM PANEL, SOUNDING DEVICES.
 ** PLEASE ALSO SHOW COMPLETE LAYOUT OF EXISTING
 DWELLING. ALL EXISTING LOCATIONS MUST BE BROUGHT UP TO
 CURRENT NFPA-72 11.5.1 FOR SMOKE ALARMS.
 PLEASE SEE FBC R313.
 ** PLEASE ALSO SEE 210.12 OF THE NEC AS THIS REQUIRES
 ARC FAULT PROTECTION.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR APPLIED SCOPE
 OF WORK PER 2005 NEC.
 THE NEC 2005 WAS GIVEN IN GENERAL AS THERE ARE MANY
 CODE SECTION WHICH NEED TO BE MET ON MINIMUM DESIGN.THE
 PERMIT APPLICATION STATES COMPLETE RE-WIRE HOWEVER
 PLANS DO NOT SHOW ANY LIGHTING, LIGHTING CONTROLS PER
 210.70.
 NO CIRCUITING OR PANEL SCHEDULES PER 408.4 PLEASE BE
 SURE ALL REQUIRED CIRCUITING PER 210.52,210.11,220 ARE
 SHOWN AND LISTED.
 PLEASE SEE 210.52 FOR MISSING RECEPTACLES.
  
 4) NOTE: PLEASE BE SURE TO INCLUDE ARC FAULT PROTECTION
 210.12
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  