| 2009-04-14 14:40:50 | BUILDING PLAN REVIEW |
| | PERMIT: 09040022 |
| | ADD: 1020 PASEO ANDORRA |
| | CONT: O/B SANTIAGO FERNANDEZ |
| | TEL: (561)835-1997 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 20079 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH THE 2009 SUPPLEMENTS. PLANS ALSO WILL BE |
| | REVIEWED TO THE 2007 EXISTING BUILDING CODE WITH 2009 |
| | SUPPLEMENTS. PLEASE UPDATE PLANS |
| | |
| | 2) 2007 EXISTING BUILDING CODE 506.2.2 A BUILDING THAT |
| | HAS SUSTAINED SUBSTANIAL STRUCTURAL DAMAGE TO THE |
| | ELEMENTS OF ITS LATERAL-FORCE RESISTING SYSTEM SHALL BE |
| | EVALUATED AND REPAIRED IN ACCORDANCE WITH THE |
| | APPLICABLE PROVISIONS OF SECTION 506.2.2.1 THROUGH |
| | 506.2.2.3. |
| | |
| | 506.2.2.1 EVALUATION . THE BUILDING SHALL BE EVALUATED |
| | BY A REGISTERED DESIGN PROFESSIONAL, AND THE EVALUATION |
| | FINDINGS SHALL BE SUBMITTED TO THE CODE OFFICIAL . THE |
| | EVALUATION SHALL ESTABLISH WHETHER THE DAMAGED |
| | BUILDING, IF REPAIRED TO ITS PREDAMAGED STATE, WOULD |
| | COMPLY WITH WITH THE PROVISIONS OF THE CODES THAT WERE |
| | IN EFFECT WHEN THE BUILDING WAS PERMITTED.WIND FORCES |
| | FOR THIS EVALUATION SHALL BE THOSE PRESCRIBED IN THE |
| | CODE THAT WERE IN EFFECT WHEN THE BUILDING WAS |
| | PERMITTED. PLEASE ALSO REVIEW 506.2.2.2 FOR EXTENT |
| | OFREPAIRS FOR COMPLIANT BUILDINGS AND 506.2.2.3. |
| | EXTENT OF REPAIRS FOR NONCOMPLIANT BUILDINGS. |
| | |
| | 3) ADDITIONAL INFORMATION IS REQUIRED, THE PERMIT |
| | APPLICATION INDICATES THAT THTE OWNER IS PULLING THE |
| | REPAIR PERMIT FOR THE STRUCTURAL PORTION OF WORK. FOR |
| | THE ROOFING PERMIT THE OWNER HAS NOT SIGNED ON NOR HAS |
| | A ROOFING CONTRACTOR SIGNED THE BOTTOM PORTION OF THE |
| | PERMIT APPLICATION FOR A ROOFING PERMIT. THE TWO ISSUES |
| | AT HAND ARE : |
| | 3A) PLANS INDICATE A 2/12 PITCH TO BE VERIFIED BY TRUSS |
| | MANUFACTURER. R905.2.7. |
| | 3B) FOR A SHINGLE ROOF THIS IS THE LEAST SLOPE THAT |
| | SHINGLES CAN BE APPLIED IS A 2:12 PITCH WITH A DOUBLE |
| | UNDERLAYMENTAND LAPPED 19 INCHES. R905.2.7. |
| | |
| | 4) SHEET A1 DOES NOT INDICATE ATTIC ACCESS PER SECTION |
| | R807.1.ATTIC ACCESS. BUILDINGS WITH COMBUSTIBLE CEILING |
| | OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M2) AND |
| | HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR MORE. |
| | PLANS FAIL TO INDICATETHE ROUGH-FRAMED OPENING SHALL |
| | NOT BE LESS THAN 22 INCHES BY 30 INCHES (559 MM BY 762 |
| | MM) AND SHALL BE LOCATED IN A HALLWAY OR OTHER READILY |
| | ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM |
| | UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE |
| | SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE |
| | MECHANICAL EQUIPMENT IS LOCATED IN ATTICS. |
| | |
| | 5) ROOF VENTILATION R806.2 MINIMUM AREA. THE TOTAL NET |
| | FREE VENTILATING AREA SHALL NOT BE LESS THAN 1/150 OF |
| | THE AREA OF THE SPACE VENTILATED EXCEPT THAT REDUCTION |
| | OF THE TOTAL AREA TO 1/300 IS PERMITTED, PROVIDED THAT |
| | AT LEAST 50 PERCENT AND NOT MORE THAN 80 PERCENT OF THE |
| | REQUIRED VENTILATING AREA IS PROVIDED BY VENTILATORS |
| | LOCATED IN THE UPPER PORTION OF THE SPACE TO BE |
| | VENTILATED AT LEAST 3 FEET (914 MM) ABOVE THE EAVE OR |
| | CORNICE VENTS WITH THE BALANCE OF THE REQUIRED |
| | VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. AS AN |
| | ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA MAY BE |
| | REDUCED TO 1/300 WHEN A VAPOR BARRIER HAVING A |
| | TRANSMISSION RATE NOT EXCEEDING 1 PERM (5.7 ?? 10-11 |
| | KG/S ?? M2 ?? PA) IS INSTALLED ON THE WARM-IN-WINTER |
| | SIDE OF THE CEILING. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |