Plan Review Notes
Plan Review Notes For Permit 09040011
Permit Number 09040011
Review Stop P
Sequence Number 1
Notes
Date Text
2009-04-22 13:44:28DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 ANSI/APSP-7
 FBC-2007(4) CHAPTER 1
  
 1. SHT A-1 GENERAL NOTES #1 INDICATES FBC-2004.
 APPLICATIONS SUBMITTED FOR PERMIT ON OR AFTER MARCH 1,
 2009 FALL UNDER THE FBC-2007 WITH 2009 SUPLEMENTS CODE.
 THE CATCH BASIN SHALL BE DESIGNED & REFERENCED PER THE
 CORRECT CODE CYCLE. SECTION 106.1.1.
  
 2. SHT A-1 DETAIL A SHOW THE MAIN DRAINS IN THE DETAIL.
 PLAN VIEW AND PLUMBING PLAN SHOWS THE DRAINS ON EACH
 SIDE OF THE CATCH BASIN, BUT DETAIL A DOES NOT SHOW THE
 DRAINS. SECTION 106.1.2. (MORE INFORMATION REQUIRED).
  
 3. SHOW THE CALCULATIONS & PIPE SIZES TO EACH MAIN
 DRAIN BRANCH LINE, (MAXIMUM 3 FT/SEC), (MAXIMUM 6
 FT/SEC IF ONE LINE OF THE PAIR IS BLOCKED). ALL OTHER
 SUCTION VELOCITIES SHALL BE 6 FT/SEC.
  
 4. SUBMIT MANUF. SPECIFICATIONS FOR THE LISTED SUCTION
 OUTLET COVERS/GRATES. ANSI/APSP-7 SECTION4.5.
  
 5. SHT A-2 GENERAL NOTES #1 STATES THE POOL SHALL
 CONFORM TO SECTION 424.2 PRIVATE SWIMMING POOLS. SINCE
 THIS POOL IS NOT LOCATED IN A RESIDENTIAL AREA, THE
 CONFORMATCE REQUIREMENTS SHALL BE PER SECTION 424.1
 PUBLIC POOLS/CATCH BASIN. PLEASE DELETE ALL REFERENCES
 TO RESIDENTIAL POOLS AND SHOW REFERENCE TO PUBLIC
 SWIMMING POOLS. SECTION 106.1.1.
  
 6. SHT A-2 PIPING DIAGRAM DOES NOT REFLECT THE PLUMBING
 PLAN SHOWN ON SHT A-1, NOR DOES IT REFLECT THE VENT
 ARRANGEMENT SHOWN ON SHT A-2. THE CONNECTION OF THE
 DRAIN LINE SHALL BE IN THE CENTER OF THE MAIN DRAINS
 AND THE VENT IS NOT SHOWN. PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  