| Plan Review Notes For Permit 09040011 |
| Permit Number |
09040011 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-16 11:38:53 | ** DENIED REVIEW** | | | | | | | | | | | | 1) NOTE: THE PERMIT APPLICATION WAS MADE AFTER MARCH | | | 1ST, 2009 WHICH PLACES THE PROJECT UNDER THE 2007 FBC | | | WITH 2009 GLITCH AMENDMENTS. PLANS STATE 2004 FBC. | | | PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS REVIEW | | | TRADE ON ELECTRICAL PLANS. | | | 2007 FBC W/2009 REVISIONS. | | | 2005 NFPA-70 | | | | | | ** THIS AHJ DOES NOT HAVE THE AUTHORITY TO REVISE AND | | | CHANGE CODE DESIGNS ON PLANS WHICH ARE DONE AND SIGNED | | | AND SEALED BY THE LICENSED DESIGNED PROFESSIONAL. | | | | | | 2) NOTE: PLEASE INDICATE CIRCUITING AND LOCATION IN | | | WHICH THESE CIRCUITS ARE BEING FED. | | | 408.4, 310.16, 240.4 | | | | | | 3) NOTE: PLEASE SEE 680.50, 56, 54, ETC FOR REQUIRED | | | GROUNDING AND PROTECTION. SOME INFORMATION IS ON PLANS | | | HOWEVER ATTACHMENT LOCATIONS ARE NOT SHOWN AND MISSING | | | SOME OTHER ATTACHMENTS. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|