Plan Review Notes
Plan Review Notes For Permit 09040011
Permit Number 09040011
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-16 11:38:53** DENIED REVIEW**
  
  
  
 1) NOTE: THE PERMIT APPLICATION WAS MADE AFTER MARCH
 1ST, 2009 WHICH PLACES THE PROJECT UNDER THE 2007 FBC
 WITH 2009 GLITCH AMENDMENTS. PLANS STATE 2004 FBC.
 PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS REVIEW
 TRADE ON ELECTRICAL PLANS.
 2007 FBC W/2009 REVISIONS.
 2005 NFPA-70
  
 ** THIS AHJ DOES NOT HAVE THE AUTHORITY TO REVISE AND
 CHANGE CODE DESIGNS ON PLANS WHICH ARE DONE AND SIGNED
 AND SEALED BY THE LICENSED DESIGNED PROFESSIONAL.
  
 2) NOTE: PLEASE INDICATE CIRCUITING AND LOCATION IN
 WHICH THESE CIRCUITS ARE BEING FED.
 408.4, 310.16, 240.4
  
 3) NOTE: PLEASE SEE 680.50, 56, 54, ETC FOR REQUIRED
 GROUNDING AND PROTECTION. SOME INFORMATION IS ON PLANS
 HOWEVER ATTACHMENT LOCATIONS ARE NOT SHOWN AND MISSING
 SOME OTHER ATTACHMENTS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  