| 2009-08-03 13:36:54 | |
| | |
| | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLANS ARE COMING BACK FOR SOME OTHER COMMENTS FROM |
| | OTHER TRADES. PLEASE ADDRESS THE FOLLOWING AT THIS |
| | TIME. |
| | ** ITEMS BELOW ARE SOME OF THE SAME ITEMS FROM PREVIOUS |
| | REVIEW. SOME ITEMS WERE REVISED HOWEVER ARE STILL IN |
| | CONFLICT WITH THE MINIMUM OF THE NATIONAL ELECTRICAL |
| | CODE. NFAP-70 2005 |
| | |
| | 1) NOTE: PLEASE COORDINATE ALL A/C EQUIPMENT, OVER |
| | CURRENT PROTECTION, BRANCH CIRCUITING ETC. |
| | MECHANICAL PLANS INDICATE NEW A/C WITH 7.5 KW AND A 25 |
| | AMP LOAD WHICH IS NOT POSSIBLE. THE 7.5 LOAD @ 240V IS |
| | 31.25AMPS. PER 424.3B THE MINIMUM OVER CURRENT |
| | PROTECTION MUST BE 125%. |
| | PLEASE SEE A/C LOAD TABLE WHICH INDICATES BOTH SYSTEMS |
| | WITH 60AMP ON HEAT AND 30AMP ON CU. THIS IS IN CONFLICT |
| | WITH THE PANEL SCHEDULE WITH 40AMP BREAKERS SHOWN FOR |
| | EACH CU. |
| | PLEASE GO OVER ALL LOADS AND CIRCUITS. |
| | 240.4,310.16, 220.60, 422.11E3, 424.3B ETC |
| | |
| | 2) NOTE: PANEL SCHEDULE AND LOAD CALCULATIONS ONLY |
| | INDICATE ONE SMALL APPLIANCE CIRCUIT AND LOAD. |
| | PLEASE SEE 210.52B1, 210.11C1, 220.52 |
| | |
| | 3) NOTE: PLEASE SEE WATER HEATER LOAD AND CONDUCTOR |
| | SIZE. PREVIOUS NOTE MENTIONED THE LOAD TO BE FIGURED AT |
| | 125% FOR FEEDER/SERVICE AND BRANCH CIRCUIT HOWEVER |
| | PLANS ARE NOW COMING BACK SHOWING A 10KW LOAD ON #10AWG |
| | WITH A 40AMP BREAKER. |
| | NONE OF THESE COORDINATE. |
| | 310.16, 240.4, 422.13 |
| | |
| | ** PANEL SCHEDULE SHOWS 30AMP BREAKER ON #10. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |