Plan Review Notes
Plan Review Notes For Permit 09030628
Permit Number 09030628
Review Stop E
Sequence Number 3
Notes
Date Text
2009-08-03 13:36:54 
  
 ** DENIED 3RD REVIEW **
  
 ** PLANS ARE COMING BACK FOR SOME OTHER COMMENTS FROM
 OTHER TRADES. PLEASE ADDRESS THE FOLLOWING AT THIS
 TIME.
 ** ITEMS BELOW ARE SOME OF THE SAME ITEMS FROM PREVIOUS
 REVIEW. SOME ITEMS WERE REVISED HOWEVER ARE STILL IN
 CONFLICT WITH THE MINIMUM OF THE NATIONAL ELECTRICAL
 CODE. NFAP-70 2005
  
 1) NOTE: PLEASE COORDINATE ALL A/C EQUIPMENT, OVER
 CURRENT PROTECTION, BRANCH CIRCUITING ETC.
 MECHANICAL PLANS INDICATE NEW A/C WITH 7.5 KW AND A 25
 AMP LOAD WHICH IS NOT POSSIBLE. THE 7.5 LOAD @ 240V IS
 31.25AMPS. PER 424.3B THE MINIMUM OVER CURRENT
 PROTECTION MUST BE 125%.
 PLEASE SEE A/C LOAD TABLE WHICH INDICATES BOTH SYSTEMS
 WITH 60AMP ON HEAT AND 30AMP ON CU. THIS IS IN CONFLICT
 WITH THE PANEL SCHEDULE WITH 40AMP BREAKERS SHOWN FOR
 EACH CU.
 PLEASE GO OVER ALL LOADS AND CIRCUITS.
 240.4,310.16, 220.60, 422.11E3, 424.3B ETC
  
 2) NOTE: PANEL SCHEDULE AND LOAD CALCULATIONS ONLY
 INDICATE ONE SMALL APPLIANCE CIRCUIT AND LOAD.
 PLEASE SEE 210.52B1, 210.11C1, 220.52
  
 3) NOTE: PLEASE SEE WATER HEATER LOAD AND CONDUCTOR
 SIZE. PREVIOUS NOTE MENTIONED THE LOAD TO BE FIGURED AT
 125% FOR FEEDER/SERVICE AND BRANCH CIRCUIT HOWEVER
 PLANS ARE NOW COMING BACK SHOWING A 10KW LOAD ON #10AWG
 WITH A 40AMP BREAKER.
 NONE OF THESE COORDINATE.
 310.16, 240.4, 422.13
  
 ** PANEL SCHEDULE SHOWS 30AMP BREAKER ON #10.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II