| 2009-07-31 14:36:43 | BUILDING PLAN REVIEW |
| | PERMIT: 09030628 |
| | ADD: 1320 N. MANGONIA DRIVE |
| | CONT: HBR DEVELOPERS, LLC |
| | TEL: (561)371-8546 |
| | |
| | FL BLD CODE= 2007 FLORIDA RESIDETIAL BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | JUNE 31,2009 |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) CONCERNS OVER LINTELS SIZE INDICATED ON SHEET A-2 |
| | AND LGRAVITY LOADING OF TRUSS A-2 FOUND ON SHEET A-5. |
| | SHEET A-2 INDICATES THE USE OF A 8"X8" LINTEL WITH 2# 3 |
| | TOP STEEL AND ONE# 5 BOTTOM STEEL SPANNING 10'-6" . |
| | 2A) CONCERN A IS THAT NO GRAVITY LOADS HAVE BEEN |
| | PROVIDED, NOR HAS THE PRODUCT APPROVAL FOR THE PRE-CAST |
| | BEEN HIGHLIGHTED INDICATING THE TYPE OF LINTEL TO BE |
| | INSTALLED AND ASSCIATED SAFE LOADS THAT THE LINTEL WILL |
| | CARRY. R606.8 LINTELS. MASONRY OVER OPENINGS SHALL BE |
| | SUPPORTEDBY STEEL LINTELS, REINFORCED CONCRETE OR |
| | MASONARY LINTELS OR MASONARY ARCHES, DESIGNED TO |
| | SUPPORT LOADS IMPOSED. THE TRUSS PACKAGE INDICATES |
| | GIRDER H8 HAS A REACTION OF 3380 AT POINTS 10 AND 17 |
| | AND A NEW NOTE ON SHEET A2 THE CONTRACTOR IS TO PROVIDE |
| | PRE-ENGINEERED SHOP DRAWINGS FROM THE MANUFACTURER FOR |
| | APPROVAL, NEITHER THE TRUSS PACKAGE NOR HAS THE LINTEL |
| | PACKAGE BEEN HIGHLIGHTED INDICATING THE SIZE OF THE |
| | LINTEL TO BE INSTALLED UNDER THE H8 GIRDER. |
| | |
| | 3-8) COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |