| Plan Review Notes For Permit 09030628 |
| Permit Number |
09030628 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-07-01 14:19:55 | PLAN DENIED | | | PLEASE PROVIDE DUCT SIZE FOR TRUNK LINE AND FLEX DUCT | | | TO BATHROOM ON MECHANICAL PLANS . | | | PLEASE SHOW LOCATION OF THE CONDENSER ON THE PLANS . | | | PLEASE PROVIDE A COPY OF THE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR EQUIPMENT . | | | PLEASE SHOW THE LOCATION OF THE RETURN AIR AND SIZE ON | | | THE PLANS . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|