Plan Review Notes
Plan Review Notes For Permit 09030628
Permit Number 09030628
Review Stop E
Sequence Number 2
Notes
Date Text
2009-06-01 11:18:03** DENIED 2ND REVIEW**
  
 SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING. THERE ARE ALSO SOME NEW ITEMS BASED ON
 CHANGES MADE TO PLANS WHICH HAVE CREATED NEW COMMENTS
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70
 2002 NFPA-72
 2007 FBC RESIDENTIAL
  
 2) NOTE: PLANS STILL CONTAIN SEVERAL NOTES WHICH
 REFLECT SMOKE DETECTORS INSTEAD OF SMOKE ALARMS. WHICH
 ONE WILL BE INSTALLED? PLEASE SEE NFPA-72 2002
  
 3) NOTE: PLANS STILL NOTE RELOCATION OF WASHER AND
 DRYER, HOWEVER ONLY ONE RECEPTACLE SHOWN AS 120V
 RECEPTACLES.
 PANEL SCHEDULE DOES NOT LIST THE REQUIRED
 WASHER/LAUNDRY CIRCUIT.
 210.11C2, 220.52, 210.
  
 4) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC.
 THERE IS A NOTE ON PLANS HOWEVER AS ALL CIRCUITS NEED
 TO BE IDENTIFIED PER 408.4, PLEASE LIST ON SCHEDULE.
 SEE COMMENT #6 BELOW.
  
 5) NOTE: SAME NOTE: STORAGE TYPE WATER HEATER MUST BE
 FIGURED AT 125% PER 422.13 SEE NEC 2005 WHICH CODE WAS
 REVISED. SEE HANDBOOK FOR LOAD ON FEEDERS AND SERVICES.
 ( LAST LINE IN COMMENTARY).
  
 6) NOTE: NEW PANEL SCHEDULE SUBMITTED. PLEASE
 COORDINATE WITH THE LOAD CALCULATIONS. THERE ARE NOW
 MULTIPLE ITEMS WHICH DO NOT COORDINATE OR MEET MINIMUM
 CODE.
 WASHER NOT ON NEW PANEL SCHEDULE.
 ONLY ONE SMALL APPLIANCE CIRCUIT.
 NO MICROWAVE ON PANEL SCHEDULE.
 NO DISHWASHER ON PANEL SCHEDULE.
 ETC.
 THERE ARE OTHER ITEMS. PLEASE SEE 408.4 AS EACH CIRCUIT
 NEEDS TO BE SPECIFIC TO THE ROOMS AND AREAS IN WHICH
 THEY FEED.
 PLEASE SEE 210.52B1, 210.11C1, 220.52 FOR MINIMUM
 CIRCUITS, LOADS, ETC.
  
 7) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS
 REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM.
  
 8) NOTE: PLEASE SEE THAT THE NEW PANEL STATES THAT IT
 WILL BE 150AMPS, HOWEVER RISER SHOWS 200AMPS AND RISER
 ALSO SHOWS A NEW 200AMP OCP FOR NEW PANELS.
  
 9) NOTE: PLEASE INCLUDE AIC RATING FOR ALL SERVICE
 EQUIPMENT PER 110.9. PLANS STATE 10K FOR BRANCH
 BREAKERS HOWEVER NOTHING FOR MAIN SERVICE.
  
 10) NOTE: PLEASE SEE REDLINED PLANS FOR TWO MISSING
 RECEPTACLES PER 210.52.
  
 11) NOTE: PLEASE SEE 424.3B AS THE OCP FOR THE AHU
 SHALL BE A MINIMUM OF 125% OF THE LOAD. LOAD SHOWN AS
 8KW WITH A 40AMP BREAKER HOWEVER 125% OF THE 8KW IS
 MORE THAN 40AMPS.
 EXISTING INDICATES A 60AMP BREAKER FOR 8KW UNIT. EITHER
 THE 60AMP IS TOO HIGH OR THE UNIT IS 10KW. PLEASE
 VERIFY. 220.
  
  
 12) NOTE: *** PLEASE REMOVE ALL OLD/VOIDED SHEETS AS
 NOTED ON PREVIOUS REVIEW AS * IMPORTANT*
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  