| Date |
Text |
| 2009-06-01 11:18:03 | ** DENIED 2ND REVIEW** |
| | |
| | SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF |
| | ADDRESSING. THERE ARE ALSO SOME NEW ITEMS BASED ON |
| | CHANGES MADE TO PLANS WHICH HAVE CREATED NEW COMMENTS |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON ELECTRICAL PLANS AT A MINIMUM. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2007 FBC RESIDENTIAL |
| | |
| | 2) NOTE: PLANS STILL CONTAIN SEVERAL NOTES WHICH |
| | REFLECT SMOKE DETECTORS INSTEAD OF SMOKE ALARMS. WHICH |
| | ONE WILL BE INSTALLED? PLEASE SEE NFPA-72 2002 |
| | |
| | 3) NOTE: PLANS STILL NOTE RELOCATION OF WASHER AND |
| | DRYER, HOWEVER ONLY ONE RECEPTACLE SHOWN AS 120V |
| | RECEPTACLES. |
| | PANEL SCHEDULE DOES NOT LIST THE REQUIRED |
| | WASHER/LAUNDRY CIRCUIT. |
| | 210.11C2, 220.52, 210. |
| | |
| | 4) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC. |
| | THERE IS A NOTE ON PLANS HOWEVER AS ALL CIRCUITS NEED |
| | TO BE IDENTIFIED PER 408.4, PLEASE LIST ON SCHEDULE. |
| | SEE COMMENT #6 BELOW. |
| | |
| | 5) NOTE: SAME NOTE: STORAGE TYPE WATER HEATER MUST BE |
| | FIGURED AT 125% PER 422.13 SEE NEC 2005 WHICH CODE WAS |
| | REVISED. SEE HANDBOOK FOR LOAD ON FEEDERS AND SERVICES. |
| | ( LAST LINE IN COMMENTARY). |
| | |
| | 6) NOTE: NEW PANEL SCHEDULE SUBMITTED. PLEASE |
| | COORDINATE WITH THE LOAD CALCULATIONS. THERE ARE NOW |
| | MULTIPLE ITEMS WHICH DO NOT COORDINATE OR MEET MINIMUM |
| | CODE. |
| | WASHER NOT ON NEW PANEL SCHEDULE. |
| | ONLY ONE SMALL APPLIANCE CIRCUIT. |
| | NO MICROWAVE ON PANEL SCHEDULE. |
| | NO DISHWASHER ON PANEL SCHEDULE. |
| | ETC. |
| | THERE ARE OTHER ITEMS. PLEASE SEE 408.4 AS EACH CIRCUIT |
| | NEEDS TO BE SPECIFIC TO THE ROOMS AND AREAS IN WHICH |
| | THEY FEED. |
| | PLEASE SEE 210.52B1, 210.11C1, 220.52 FOR MINIMUM |
| | CIRCUITS, LOADS, ETC. |
| | |
| | 7) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS |
| | REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM. |
| | |
| | 8) NOTE: PLEASE SEE THAT THE NEW PANEL STATES THAT IT |
| | WILL BE 150AMPS, HOWEVER RISER SHOWS 200AMPS AND RISER |
| | ALSO SHOWS A NEW 200AMP OCP FOR NEW PANELS. |
| | |
| | 9) NOTE: PLEASE INCLUDE AIC RATING FOR ALL SERVICE |
| | EQUIPMENT PER 110.9. PLANS STATE 10K FOR BRANCH |
| | BREAKERS HOWEVER NOTHING FOR MAIN SERVICE. |
| | |
| | 10) NOTE: PLEASE SEE REDLINED PLANS FOR TWO MISSING |
| | RECEPTACLES PER 210.52. |
| | |
| | 11) NOTE: PLEASE SEE 424.3B AS THE OCP FOR THE AHU |
| | SHALL BE A MINIMUM OF 125% OF THE LOAD. LOAD SHOWN AS |
| | 8KW WITH A 40AMP BREAKER HOWEVER 125% OF THE 8KW IS |
| | MORE THAN 40AMPS. |
| | EXISTING INDICATES A 60AMP BREAKER FOR 8KW UNIT. EITHER |
| | THE 60AMP IS TOO HIGH OR THE UNIT IS 10KW. PLEASE |
| | VERIFY. 220. |
| | |
| | |
| | 12) NOTE: *** PLEASE REMOVE ALL OLD/VOIDED SHEETS AS |
| | NOTED ON PREVIOUS REVIEW AS * IMPORTANT* |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |