Plan Review Notes
Plan Review Notes For Permit 09030628
Permit Number 09030628
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-10 15:51:01** DENIED**
  
 1) NOTE: PLANS ARE STATING ALL DESIGNS PER 2004 FBC.
 ANY PLANS SUBMITTED FOR PER AFTER MARCH 1ST, 2009 MUST
 BE UNDER THE NEW 2007 FBC WITH 2009 AMENDMENTS.
 PLEASE BE SURE THE FOLLOWING CODES ARE STATED ON PLANS
 AT A MINIMUM.
 2005 NFPA-70
 2002 NFPA-72
 2007 FBC RESIDENTIAL
  
 2) NOTE: PLANS STATE SMOKE DETECTORS. SMOKE DETECTORS
 ARE UNITS WHICH ONLY DETECT AND DO NOT SOUND. PLEASE
 SEE DEFINITIONS IN NFPA-72 2002. PLEASE KNOW THAT SMOKE
 ALARMS ARE DEVICES WHICH DETECT AND SOUND. IF THESE ARE
 INDEED SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH FIRE
 ALARM PANEL, SOUNDING DEVICES.
 ** PLEASE ALSO SHOW COMPLETE LAYOUT OF EXISTING
 DWELLING. ALL EXISTING LOCATIONS MUST BE BROUGHT UP TO
 CURRENT NFPA-72 11.5.1 FOR SMOKE ALARMS.
 PLEASE SEE FBC R313.
 ** PLEASE ALSO SEE 210.12 OF THE NEC AS THIS REQUIRES
 ARC FAULT PROTECTION.
  
 3) NOTE: PLEASE SHOW LOCATION OF RELOCATED WASHER AND
 DRYER OUTLET. PLANS STATE THIS HOWEVER NOT SHOWN.
 210.52
  
 4) NOTE: PLEASE BE SURE TO LIST THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS PER 210.12 OF THE 2005 NEC.
 THERE IS A NOTE ON PLANS HOWEVER AS ALL CIRCUITS NEED
 TO BE IDENTIFIED PER 408.4, PLEASE LIST ON SCHEDULE.
 SEE COMMENT #6 BELOW.
  
 5) NOTE: STORAGE TYPE WATER HEATER MUST BE FIGURED AT
 125% PER 422.13
  
 6) NOTE: PANEL SCHEDULE NOTES ONLY 1-GENERAL
 LIGHTING/RECEPTACLE CIRCUIT FOR THE HOUSE. PLEASE SEE
 408.4 AS EACH CIRCUIT NEEDS TO BE SPECIFIC TO THE ROOMS
 AND AREAS IN WHICH THEY FEED.
  
 7) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS
 REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM.
  
 8) NOTE: THE GFI NOTE ON PLANS WITH RESPECT TO DISTANCE
 REQUIREMENT WITHIN 15FT OF POOL IS NOT CODE COMPLIANT.
 PLEASE SEE 210.8A3 AND 680.22 FOR REQUIRED GFI
 PROTECTION OF ALL OUTSIDE RECEPTACLES ALONG WITH
 DISTANCES FROM POOLS.
  
 9) NOTE: PLEASE INCLUDE AIC RATING FOR ALL SERVICE
 EQUIPMENT PER 110.9
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  