2009-04-14 11:16:48BUILDING PLAN REVIEW
 PERMIT: 09030628
 ADD: 1320 N. MANGONIA DRIVE
 CONT: HBR DEVELOPERS, LLC
 TEL: (561)371-8546
  
 FL BLD CODE= 2007 FLORIDA RESIDETIAL BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER MARCH 1ST, 2007 SHALL BE REVIEWED TO
 THE 2007 FBC RESIDENTIAL BUILDING WITH THE 2009
 SUPPLEMENTS AND 2007 EXISTING BUILDING CODE CHAPTER 10
 ADDITIONS. THE COVERSHEET A-1 NEEDS TO BE UP DATED.
  
 2) CONCERNS OVER LINTELS SIZE INDICATED ON SHEET A-2
 AND LGRAVITY LOADING OF TRUSS A-2 FOUND ON SHEET A-5.
 SHEET A-2 INDICATES THE USE OF A 8"X8" LINTEL WITH 2# 3
 TOP STEEL AND ONE# 5 BOTTOM STEEL SPANNING 10'-6" .
 2A) CONCERN A IS THAT NO GRAVITY LOADS HAVE BEEN
 PROVIDED, NOR HAS THE PRODUCT APPROVAL FOR THE PRE-CAST
 BEEN HIGHLIGHTED INDICATING THE TYPE OF LINTEL TO BE
 INSTALLED AND ASSCIATED SAFE LOADS THAT THE LINTEL WILL
 CARRY. R606.8 LINTELS. MASONRY OVER OPENINGS SHALL BE
 SUPPORTEDBY STEEL LINTELS, REINFORCED CONCRETE OR
 MASONARY LINTELS OR MASONARY ARCHES, DESIGNED TO
 SUPPORT LOADS IMPOSED.
  
 2B) CONCERN B, IS UASUALLY TRUSS LAYOUT SHEETS INDICATE
 THE JACKS STARTING AT 1', 3', 5',& 7' BEING THE GIRDER
 OR TRUSS THAT WILL PICK UP THE ADDITIONAL GRAVITY
 LOADING OF THE JACKS. IF THE JACK TRUSSES
 CANTILEVER OVER THE LINTEL 2'-0" THE LOADING WILL
 BASICALLY BALANCE OUT AT 4'-0" BACK FROM THE BEGINING
 OF THE TRUSS. FROM 4'-0 TO THE GIRDER TRUSS LOCATED AT
 7'-0 PLUS THE 1'-0" TRIBUTARY AREA FROM THE OTHER SIDE
 OF THE TRUSS WOULD MEAN A 4'-0" TRIBUTARY AREA PER FOOT
 IS BEING CARRIED AT THIS POINTMULTIPLY THIS BY 1/2 THE
 SPAN AND AT 60 PSF WOULD BE A GRAVITY LOAD ON EACH END
 OF 4560 GRAVITY LOAD AT EACH END OF THE TRUSS, PLEASE
 INDICATE WHICH TYPE OF LINTEL WILL BE USED TO CARRY
 THIS LOADING. PLEASE PROVIDE TRUSS DRAWINGS PER
 R802.1.6.1 TRUSS DESIGN DRAWINGS,
 R802.1.6 WOOD TRUSSES.
 R802.1.6.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH
 SECTION R802.1.6.1, SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. TRUSS
 DESIGN DRAWINGS SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS DESIGN DRAWING SHALL
 BE PROVIDED WITH THE SHIPMENT OF TRUSSES DELIVERED TO
 THE JOBSITE.
 1. DESIGN WIND SPEED AND EXPOSURE CATEGORY.
 2. SLOPE OR DEPTH, SPAN AND SPACING.
 3. LOCATION OF ALL JOINTS.
 4. REQUIRED BEARING WIDTHS.
 5. DESIGN LOADS AS APPLICABLE.
 5.1. TOP CHORD LIVE LOAD.
 5.2. TOP CHORD DEAD LOAD.
 5.3. BOTTOM CHORD LIVE LOAD.
 5.4. BOTTOM CHORD DEAD LOAD.
 5.5. CONCENTRATED LOADS AND THEIR POINTS OF
 APPLICATION.
 5.6. CONTROLLING WIND AND EARTHQUAKE LOADS.
 6. ADJUSTMENTS TO LUMBER AND JOINT CONNECTOR DESIGN
 VALUES FOR CONDITIONS OF USE.
 7. EACH REACTION FORCE AND DIRECTION.
 8. JOINT CONNECTOR TYPE AND DESCRIPTION (E.G., SIZE,
 THICKNESS OR GAUGE) AND THE DIMENSIONED LOCATION OF
 EACH JOINT CONNECTOR EXCEPT WHERE SYMMETRICALLY LOCATED
 RELATIVE TO THE JOINT INTERFACE.
 9. LUMBER SIZE, SPECIES AND GRADE FOR EACH MEMBER.
 10. CONNECTION REQUIREMENTS FOR:
 10.1. TRUSS TO TRUSS GIRDER.
 10.2. TRUSS PLY TO PLY.
 10.3. FIELD SPLICES.
 11. CALCULATED DEFLECTION RATIO AND/OR MAXIMUM
 DESCRIPTION FOR LIVE AND TOTAL LOAD.
 12. MAXIMUM AXIAL COMPRESSION FORCES IN THE TRUSS
 MEMBERS TO ENABLE THE BUILDING DESIGNER TO DESIGN THE
 SIZE, CONNECTIONS AND ANCHORAGE OF THE PERMANENT
 CONTINUOUS LATERAL BRACING. FORCES SHALL BE SHOWN ON
 THE TRUSS DESIGN DRAWING OR ON SUPPLEMENTAL DOCUMENTS.
 13. REQUIRED PERMANENT TRUSS MEMBER BRACING LOCATION.
  
 3) SHEET A-3 INDICATES AT THE TUB THE WINDOW SILL IS
 LESS THAN 60" ABOVE THE STANDING SURFACE OF THE TUB
 MAKING THIS WINDOW A HAZARDOUS LOCATION PER:
 R308.4 HAZARDOUS LOCATIONS.THE FOLLOWING SHALL BE
 CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE
 PURPOSES OF GLAZING:
  
 R308.4 (5).GLAZING IN DOORS AND ENCLOSURES FOR HOT
 TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND
 SHOWERS. GLAZING IN ANY PART OF A BUILDING WALL
 ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED
 EDGE OF THE GLAZING IS LESS THAN 60 INCHES (1524 MM)
 MEASURED VERTICALLY ABOVE ANY STANDING OR WALKING
 SURFACE. PLEASE UPDATE WINDOW SCHEDULE FOUND ON A2
 WINDOW
 H32 TO BE SAFETY GLAZED PER TABLE R 308.3 CATEGORY
 CLASS II.
  
 4) SHEET A-3 NOR A-4 INDICATE THE USE OF VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. AS AN
 ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA MAY BE
 REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING A
 TRANSMISSION RATE NOT EXCEEDING 1 PERM (57.4 MG/S ?? M2
 ?? PA) IS INSTALLED ON THE WARM SIDE OF THE CEILING.
 R806.2
  
 5) SHEET A-2 IS MISSING ATTIC ACCESS IN THE NEW
 ADDITION. R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M2) AND
 HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 6A) PRODUCT APPROVAL 06-0606.05 BERMUDA CONCRETE FLAT
 TILE PLEASE INDICATE HOW TILE WILL BE FASTENED TO THE
 UNDERLAYMENT.R905.3.7 TILE SHALL BE APPLIED IN
 ACCORDANCE WITH THIS CHAPTER AND THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, OR RECOMMENDATIONS OF THE
 FRSA/TRI 07320 BASED ON THE FOLLOWING:
 ATTACHMENT. CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH FRSA/TRI INSTALLATION
 MANUAL 07320.
 TABLE R905.3.7 CLAY AND CONCRETE TILE ATTACHMENT.
 RESERVED.
  
 6B) R905.3.7.1. HIP AND RIDGE TILES. HIP AND RIDGE
 TILES SHALL BE INSTALLED IN ACCORDANCE WITH FRSA/TRI
 07320 MANUAL.7) .PROVIDE HIP AND RIDGE ATTACHMENT
 INFORMATION NOT FOUND IN NOA.
  
 7) OWES STATE RADON FEES OF $10.30 TO BE PAID BEFORE
 PERIMT ISSUANCE.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  