| 2009-04-09 16:15:37 | *****DENIED***** |
| | |
| | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE |
| | (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION |
| | AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION - SHALL |
| | BE REFERENCED. |
| | |
| | 3. THE PROJECT SITE ADDRESS, INCLUDING UNIT NUMBER, |
| | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN |
| | SHEET. |
| | |
| | 4. LIST THE PROJECT SITE'S OCCUPANCY TYPE (I.E. |
| | BUSINESS, RESIDENTIAL, MERCANTILE), OCCUPANT LOAD, AND |
| | OTHER PERTINENT INFORMATION NECESSARY FOR A THOROUGH |
| | PLAN REVIEW. |
| | |
| | 5. SPECIFY THE INTERIOR FINISH MATERAILS FOR THE NEW |
| | WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 6. PLANS INDICATE THAT A NEW DOOR TO THE EXISTING |
| | STAIRCASE WILL BE INSTALLED, PROVIDE WIDTH AND HEIGHT |
| | DIMENSIONS OF THE SAID DOOR. |
| | |
| | 7. WILL THE PROJECT SCOPE OF WORK HAVE CAUSE FOR THE |
| | SPRINKLER HEADS TO BE REMODELED? THIS WRITER WAS UNABLE |
| | TO LOCATE SUCH DEVICES IN THE ORIGINAL FLOOR PLAN. |
| | |
| | 8. PLANS INDICATE THAT SMOKE DETECTORS (SD) ARE |
| | INSTALLED. PLEASE BE ADVISED THAT SMOKE DETECTOR ARE |
| | TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS |
| | SMOKE ALARMS (SA) SHALL ONLY SOUND/ALERT THE OCCUPANT |
| | OF THE SAID DWELLING UNIT AND NOT ACTUATE THE |
| | BUILDING'S FIRE ALARM SYSTEM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE THE COMMENTS WERE ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |