| Date |
Text |
| 2009-04-13 12:16:38 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF |
| | PLANS BOUND TOGETHER. |
| | PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM CODES ARE |
| | STATED ON PLANS. |
| | 2007 FBC W/ 2009 REVISIONS. |
| | 2006 NFPA-101 |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: THE SCOPE OF WORK AS APPLIED MAY NOT BE DONE |
| | AS AN OWNER/BUILDER PER FS 489. THIS HAS BEEN CONFIRMED |
| | WITH THE LAW DEPARTMENT AND THE STATE OF FLORIDA |
| | ATTORNEY GENERALS OFFICE. |
| | PLEASE OBTAIN LICENSED CONTRACTORS PER FS 489. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR ALL CURRENT |
| | CODES IN AFFECT AFTER MARCH 1ST, 2009. PLEASE SEE |
| | CHAPTER 3 OF THE FBC TO STATE USE AND OCCUPANCY. |
| | PLANS STATE SKINCARE HOWEVER USE FOR ITEMS SUCH AS |
| | OTHER BEAUTY NAIL CARE ETC WILL AFFECT MINIMUM CODE |
| | COMPLIANCE DESIGNS. |
| | |
| | 4) NOTE: LIGHTING CONTROLS PER 13-415.1.AB.1.1,.1.2 |
| | REQUIRED. |
| | |
| | 5) NOTE: PRESCRIPTIVE LIGHTING PERFORMANCE NEEDS TO BE |
| | SHOWN PER 13-415.AB.5. THIS IS ONLY FOR NEW BEING |
| | INSTALLED. |
| | THE PLANS DO NOT INDICATE SPECIFIC LIGHTING. |
| | |
| | 6) NOTE: PLEASE COMPLETE CIRCUITING TO NEW RECEPTACLES |
| | AND LIGHTING. PLEASE INDICATE WHERE THEY ARE BEING FED |
| | FROM. WHAT SIZE CIRCUIT, OVER CURRENT PROTECTION ETC. |
| | 408.4, 240.4, 310.16 |
| | |
| | 7) NOTE: PLANS TO BE SUBMITTED SHALL BE DESIGNED BY |
| | REQUIRED DESIGNER PER FS 471.003, 481.221. AS THE SCOPE |
| | MAY BE REVISED ALONG WITH VALUATION ON THE FOLLOWING |
| | COMMENT THE PLANS SUBMITTED DO NOT MEET MINIMUM |
| | REQUIREMENTS. |
| | PLEASE ALSO SEE FBC 106.1.1, 106.1, ETC AS PLANS |
| | SUBMITTED MAY NOT BE CUT AND PASTE OF PIECES OF OTHER |
| | PLANS, DRAWN IN PENCIL ETC. |
| | ONE SET OF PLANS SUBMITTED ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | 8) NOTE: THE APPLIED VALUE IS LOW FOR THE SCOPE OF WORK |
| | SHOWN ON PLANS WHICH WILL ALSO BE REQUIRED TO MEET |
| | MINIMUM CODE. |
| | THE VALUE FOR COMPLETE SCOPE MUST INCLUDE DESIGN COSTS, |
| | LABOR, EQUIPMENT, MATERIALS EVEN IF ANY OF THESE ITEMS |
| | ARE OWNER SUPPLIED. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |