| 2009-04-14 16:15:22 | REVIEW #: 1ST **PLAN CHECK ONLY** |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: PLANS SUBMITTED FOR PLANS REVIEW ONLY. NO PERMIT |
| | APPLICATION SUBMITTED AT THIS TIME. |
| | |
| | 1. PAGE M-3: EXHAUST FAN SCHEDULE CALLS FOR EF-1 AND |
| | EF-2 WHILE PAGE M-3 SHOWS EF-4 AND EF-5. PLEASE |
| | COORIDINATE PLANS AND EQUIPMENT SCHEDULES. |
| | |
| | 2. PAGE M-3: MECHANICAL NOTES 15, 16 AND 18 REFERENCE |
| | THE 2004 FBC. PLEASE UPDATE ALL CODES TO REFERENCE THE |
| | 2007 FBC, WHICH IS IN EFFECT AS OF MARCH 1, 2009. |
| | |
| | 3. PAGE M-4: DIFFUSER DETAIL SHOWS FLEX DUCT SUPPORTED |
| | BY 1 INCH BAND. ALL SUPPORTS FOR FLEX DUCT SHALL BE |
| | MIN. 1 1/2" WIDE MINIMUM PER FBC-M 603.5.6.6. |
| | |
| | 4. PAGE M-4: ROOF CURB DETAILS SHOW ATTACHMENT BASED ON |
| | ROOF JOIST AND METAL DECK CONSTRUCTION. ARCHITECTURAL |
| | PLANS INDICATE THIS BUILDING ROOF STRUCTURE IS CONCRETE |
| | DECK/PLANKS. PLEASE PROVIDE CURB INSTALLATION DETAIL |
| | APPROPRIATE FOR THE EXISTING CONSTRUCTION, DESIGNED FOR |
| | WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 5. PAGE M-4 AND E-1.01: THESE PAGES SHOW DUCT SMOKE |
| | DETECTOR INSTALLED IN THE RETURN DUCT WHILE PAGE M-1 |
| | SHOWS THE DUCT SMOKE DETECTOR INSTALLED IN THE SUPPLY |
| | DUCT. PLEASE COORDINATE PLANS AND DETAILS, SHOWING THE |
| | DUCT SMOKE DETECTOR BEING INSTALLED IN THE SUPPLY DUCT |
| | IN ACCORDANCE WITH FBC-M 606.2.1. |
| | |
| | 6. PROVIDE MANUFACTURER'S DATA FOR THE PROPOSED RTU |
| | SHOWING IT IS DESIGNED FOR WIND RESOSTANCE. MECHANICAL |
| | APPLIANCES EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M |
| | 301.12. |
| | |
| | 7. ON DOWN-FLOW UNITS (SUCH AS THE PROPOSED RTU), A |
| | WATER-LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE |
| | THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M |
| | 307.2.3.1. THIS DEVICE SHALL SHUT OFF THE EQUIPMENT |
| | SERVED IN THE EVENT THAT THE PRIMARY DRAIN BECOMES |
| | RESTRICTED. EXTERNALLY INSTALLED DEVICES AND DEVICES |
| | INSTALLED IN THE DRAIN LINE SHALL NOT BE PERMITTED. |
| | |
| | NOTE: MECHANICAL PLANS WERE NOT SIGNED AND SEALED BY |
| | THE ENGINEER. ONCE PLANS ARE SUBMITTED FOR PERMIT, |
| | PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN |
| | PROFESSIONAL IN ACCORDANCE WITH FS 471 AND FAC RULE |
| | 61G15-23.002. |
| | |