| Plan Review Notes For Permit 09030588 |
| Permit Number |
09030588 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-16 08:42:57 | ** DENIED** | | | | | | | | | | | | 1) NOTE: PLEASE SEE NEC 250.6 AND 250 AS RISER SHOWS AN | | | EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF | | | DISCONNECT WHICH IS NOT PERMITTED. THIS 3/0 CONDUCTOR | | | WOULD CREATE OBJECTIONABLE CURRENTS. | | | | | | 2) NOTE: PLEASE PROVIDE LOCATION OF METERING EQUIPMENT. | | | PLEASE SEE FPL MINIMUM SERVICE STANDARDS. IF EXISTING | | | PLEASE SHOW. | | | | | | 3) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY AND HAVE | | | NOT BEEN SUBMITTED FOR PERMIT BY A LICENSED CONTRACTOR. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|