2009-09-17 10:19:21MECHANICAL REVISIONS TO SHEET M-1 ARE DENIED.
  
 1) THE MECHANICAL REVISIONS ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ARCHITECT THAT SEALED THE ORIGINAL
 MECHANICAL DRAWINGS. FS 481.
  
 2) THE PLANS ARE NOT CLEAR AND LEGIBLE. THE PLANS HAVE
 "DEMO LICENSE NOT FOR RESALE" PRINTED ALL OVER THEM.
 SUBMIT CLEAR LEGIBLE DRAWINGS. FBC 106.1.1
  
 3) THE REVISIONS ARE NOT CLEARLY IDENTIFIED ON THE
 DRAWING. ITEMS THAT APPEAR TO BE ELIMINATED OR MOVED
 ARE STILL SHOWN ON THE PLANS IN THE ORIGINAL LOCATIONS.
 PLEASE CORRECT. FBC 106.1.1
  
 4) HAND WRITTEN CHANGES AND NOTATIONS ON THE PLANS CAN
 ONLY BE DONE BY THE DESIGNER OF RECORD. FS 481
  
 5) THE REVISION NOTES THAT THE CONDENSING UNIT ON THE
 EXTERIOR IS TO BE RELOCATED. INDICATE THE NEW LOCATION
 OF THE CONDENSING UNIT ON THE PLANS. FBC 106.1.1 THE
 NEW LOCATION WILL REQUIRE THE APPROVAL OF THE ZONING
 DEPARTMENT. PROVIDE SURVEY OR SITE PLAN INDICATING THE
 NEW LOCATION AND THE DISTANCES FROM PROPERTY LINES.
 CONTACT THE ZONING DEPARTMENT FOR THEIR REQUIREMENTS AT
 561-822-1435.
  