| Plan Review Notes For Permit 09030575 |
| Permit Number |
09030575 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-08 09:08:40 | 2007 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO (2) COPIES OF ENERGY CALCULATIONS AND | | | MANUAL J CALCULATIONS AS REQUIRED AS REQUIRED BY 2007 | | | FBC R N1100. | | | | | | 2) REVISE PLANS TO COMPLY WITH 2007 FBC R M1602.4 | | | BALANCED RETURN AIR. | | | | | | 3) UPDATE REFERENCES TO FMC CODE SECTIONS TO THE 2007 | | | FMC AS SOME HAVE BEEN CHANGED. SEE REDLINED PLAN. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|