| Plan Review Notes For Permit 09030568 |
| Permit Number |
09030568 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-04-03 15:35:53 | ** DENIED ** | | | | | | | | | 1) NOTE: ONE SET OF SEALED PLANS CONTAIN A *RUBBER | | | STAMP* IN LIEU OF AN ORIGINAL SIGNATURE WHICH IS NOT | | | PERMITTED PER FS 481.221 | | | | | | 2) NOTE: ELECTRICAL RECEPTACLES ARE TOO CLOSE TO | | | POOL/WATERS EDGE. PLEASE SEE 680.22. | | | | | | 3) NOTE: PLEASE SEE 680.26 FOR REQUIRED DETAIL FOR | | | BONDING OF ALL METAL PARTS WITHIN AREA OF POOL. | | | | | | 4) NOTE: PLEASE BE SURE PLANS CONTAIN ALL RELEVANT | | | ADOPTED CODES STATED FOR MINIMUM DESIGNS. | | | FS 553.73 | | | FBC 2007 W/ 2009 GLITCH AMENDMENTS. | | | 2005 NFPA-70 | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|