Plan Review Notes
Plan Review Notes For Permit 09030568
Permit Number 09030568
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-03 15:35:53** DENIED **
  
  
 1) NOTE: ONE SET OF SEALED PLANS CONTAIN A *RUBBER
 STAMP* IN LIEU OF AN ORIGINAL SIGNATURE WHICH IS NOT
 PERMITTED PER FS 481.221
  
 2) NOTE: ELECTRICAL RECEPTACLES ARE TOO CLOSE TO
 POOL/WATERS EDGE. PLEASE SEE 680.22.
  
 3) NOTE: PLEASE SEE 680.26 FOR REQUIRED DETAIL FOR
 BONDING OF ALL METAL PARTS WITHIN AREA OF POOL.
  
 4) NOTE: PLEASE BE SURE PLANS CONTAIN ALL RELEVANT
 ADOPTED CODES STATED FOR MINIMUM DESIGNS.
 FS 553.73
 FBC 2007 W/ 2009 GLITCH AMENDMENTS.
 2005 NFPA-70
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  