| 2009-05-12 13:09:15 | *****DENIED***** |
| | |
| | |
| | 1. ON THE COVER SHEET (A0.0), AMEND THE FOLLOWING |
| | INFORMATION IN THE PROJECT TEAM SECTION: BUILDING |
| | DEPARTMENT - 401 CLEMATIS STREET (ADDRESS); FIRE |
| | DEPARTMENT - 500 NORTH DIXIE HIGHWAY (ADDRESS), |
| | 561-804-4724 (TELEPHONE). |
| | |
| | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| | REFERENCED IN ADDITION TO THE 2007 FLORIDA FIRE |
| | PREVENTION CODE. MAKE THE NECESSARY CORRECTIONS ON |
| | SHEET A0-0 IN THE CODE INFORMATION SECTION. |
| | |
| | 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. ADD 2004 EDITION TO THE LISTED NFPA 241 IN THE |
| | CODE INFORMATION SECTION. |
| | |
| | 4. IT IS NOTED ON SHEETS A1-1 & A1-2 THAT ALL WORK WILL |
| | BE CONDUCTED DURING THE SPECIFIED TIME THAT THE STORE |
| | CLOSES AND THEN RE-OPENS THE FOLLOWING DAY. THE FIRE |
| | PROTECTION SYSTEMS IN THIS BUILDING SHALL BE MAINTAINED |
| | OPERATIONAL AT ALL TIMES DURING THE ALTERATION. WHEN/IF |
| | IT IS NECESSARY FOR THE SYSTEM TO BE MODIFIED AND/OR |
| | SHUT DOWN, THE FIRE PREVENTION BUREAU SHALL HAVE THE |
| | AUTHORITY TO REQUIRE ALTERNATIVE MEASURES OF PROTECTION |
| | UNTIL THE SYSTEM IS RETURNED TO SERVICE. |
| | |
| | 5. ON SHEET E0.0, MAKE NECESSARY CORRECTIONS TO THE |
| | APPLICABLE CODES SECTION AS FOLLOWS: REFERENCE 2007 |
| | (NOT 2005) FLORIDA FIRE PREVENTION CODE, DELETE |
| | REFERENCE TO 2003 NFPA-72. |
| | |
| | 6. SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN THE TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |