Plan Review Notes
Plan Review Notes For Permit 09030551
Permit Number 09030551
Review Stop B
Sequence Number 1
Notes
Date Text
2009-04-27 16:16:20BUILDING PLAN REVIEW
 PERMIT: 09030551
 ADD: 2497 OKEECHOBEE BLVD
 CONT: WARWICK CONSTRUCTION
 TEL: (954)553-1701 JEANETTE CAMPBELL
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009
  
 2) PLEASE CORRECT ALL REFRENCES TO THE 2004 FBC WE ARE
 CURRENTLY REVIEWING PLANS TO THE 2007 FBC WITH 2009
 SUPPLEMENTS, TENANT SPACES 2007 EXISTING BUILDING CODE/
 WITH 2009 SUPPLEMENTS.
 PLEASE IDENTIFY TO WHAT LEVEL OF ALTERATION THE PLANS
 WERE DESIGNED TO. EXISTING BUILDING CODE 401.4 A DESIGN
 PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 3) PLEASE UPDATE THE ENERGY FORMS FORM 400B- 2004
 V2.5THE NEW FORMS WOULD BE 400B-07 . 13-400.4.ABC
 REPORTING.
  
 4) SHEET A0-2 IN NOTES TRAVEL DISTANCE, NUMBER OF EXITS
 & EXIT DOOR ARRANGEMENTS ALL INDICATE THE CBC 2007 THE
 PLANS SHOULD BE DESIGNED UNDER THE FLORIDA EXISTING
 BUILDING CODE OR THE FLORIDA BUILDING CODE, BUILDING
 BUT THIS IS A TENANT BUILDOUT AND SHOULD BE DESIGNED
 UNDER THE FLORIDA EXISTING BUILDING CODE.
  
 5) SHEET A5-0 RESTROOM DETAILS INDICATE THEY ARE DRAWN
 TO A 3/4 INCH SCALE IT APPEARS THE ENTRY DOORS TO THE
 RESTROOM ARE ONLY 2'-0" WIDE, RECHECK THE SCALE DRAWN
 TO. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A5-0 RESTROOM DETAIL PLEASE INDICATE THE CLEAR
 FLOOR SPACE FOR THE WATER FOUNTAIN BETWEEN THE
 RESTROOMS. 11-4.15.5.
  
 7) SHEET A6-2 THE HC FITTING ROOM PLEASE REVIEW THE
 SCALE OF THE DRAWINGS. THEY INDICATE 1"=1'-0". 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) ELEVATION SHEETS INDICATE REMOVAL AND NEW SIGNAGE
 REQUIRES A SEPERATE PERMIT FOR NEW SIGNAGE.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2009-04-09 08:33:07PLANS ON HOLD FOR NON-PAYMENT. CALLED CONTRACTOR
 4/07/09
 4/09/09 PLANS PLACED OUT FRONT FOR NON PAYMENT.