Plan Review Notes
Plan Review Notes For Permit 09030515
Permit Number 09030515
Review Stop P
Sequence Number 1
Notes
Date Text
2009-04-01 11:18:43DENIED
 REFERENCE:
 FBC-2007 PLUMBING W/2009 SUPPLEMENTS
 FBC-2004 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. PLANS SHALL BE SUBMITTED IN BOUND SETS, NOT LOOSE
 SHEETS AS SUBMITTED. (MINIMUM 2 SETS) SECTION 106.1.
  
 2. PLANS SHALL INDICATE THE CODE CRITERIA. PLANS SHALL
 BE DESIGNED TO THE FBC-2007 W/2009 SUPPLEMENTS.
  
 3. INDICATE OCCUPANCY ON PLANS. SECTION 106.1.1.
  
 4. MOST OCCUPANCIES REQUIRE A DRINKING FOUNTAIN. TABLE
 403.1. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 FIXTURE AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 5. SOME OCCUPANCIES REQUIRE A SERVICE SINK. DEPENDING
 ON THE COMMENT RESPONSE AND INFORMATION RECIEVED, MORE
 COMMENTS MAY BE FORTHCOMMING. PLANS DO NOT APPEAR TO BE
 100% AT THIS TIME. TABLE 403.1.
  
 6. NEW FIXTURES, WHERE REQUIRED SHALL REQUIRE A
 SANITARY ISOMETRIC RISER DIAGRAM AND A WATER ISOMETRIC
 RISER DIAGRAM. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved