Plan Review Notes
Plan Review Notes For Permit 09030515
Permit Number 09030515
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-04-08 16:01:53*****DENIED*****
  
  
 1. PLEASE LIST THE OCCUPANCY TYPE (BUSINESS,
 MERCANTILE, INDUSTRIAL, STORAGE, ETC.) AND THE OCCUPANT
 LOAD FOR THIS BUILDING.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION
 AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION) SHALL BE
 REFERENCED.
  
 4. SHOW/DISPLAY THE EXIT LIGHTS, EMERGENCY LIGHTS, FIRE
 EXTINGUISHER(S), FIRE ALARM DEVICES, AND FIRE SPRINKLER
 HEADS FOR THE PROPOSED FLOOR PLAN.
  
 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. WILL THE SCOPE OF WORK HAVE CAUSE FOR FIRE SPRINKLER
 HEADS AND / OR FIRE ALARM DEVICES TO BE REVISED? IF SO,
 SEPARATE PERMIT AND SHOP DRAWINGS SHALL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722