2009-04-13 08:26:35** DENIED**
  
 1) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF
 PLANS BOUND TOGETHER.
 PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM CODES ARE
 STATED ON PLANS.
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA_72
  
 2) NOTE: LIGHTING CONTROLS PER 13-415.1.AB.1.1,.1.2
 REQUIRED.
  
 3) NOTE: PRESCRIPTIVE LIGHTING PERFORMANCE NEEDS TO BE
 SHOWN PER 13-415.AB.5. THIS IS ONLY FOR NEW BEING
 INSTALLED.
 THE PLANS DO NOT INDICATE SPECIFIC LIGHTING.
  
 4) NOTE: PLEASE COMPLETE CIRCUITING TO NEW RECEPTACLES
 AND LIGHTING. PLEASE INDICATE WHERE THEY ARE BEING FED
 FROM. WHAT SIZE CIRCUIT, OVER CURRENT PROTECTION ETC.
 408.4, 240.4, 310.16
  
 5) NOTE: ADDRESS ON PLANS STATES * OLD OKEECHOBEE RD*
 ACTUAL LOCATION IS JUST * OKEECHOBEE RD*. THIS OFFICE
 IS AWARE THAT STREET SIGNS ETC MAY STATE * OLD* HOWEVER
 ACTUAL LEGAL ADDRESS DOES NOT INCLUDE THIS WORDING.
 PLEASE ADJUST PLANS.
 FAC61G1-16.004
 FBC 106.5
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  