| 2009-04-06 16:32:28 | REVIEW |
| | PERMIT: 09030515 |
| | ADD: 1807 OKEECHOBEE ROAD |
| | CONT: T.A.P.E. CONSTRUCTION |
| | TEL: (561)1807 OLD OKEECHOBEE RD. |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO |
| | THE 2007 FBC BUILDING WITH THE 2009 SUPPLEMENTS. |
| | |
| | 3) SUBMIT AN EXISTING FLOOR PLAN OF THE EXISTING SPACE |
| | TO BE ALTERED SHOWING WHAT WALL WILL BE DEMOED ALONG |
| | WITH A PROPOSED FLOOR PLAN WITH THE NEW LAYOUT OF THE |
| | SPACE. |
| | |
| | 4) SUBMIT 2 COMPLETE SETS OF PLANS BOUNDED NOT LOOSE |
| | SHEETS 106.1 |
| | |
| | 5) THE PLANS SHALL INDICATE THE TYPE OF CONSTRUCTION |
| | PER CHAPTER 6 AND TABLE 503, THE USE AND OCCUPANCY PER |
| | CHAPTER 3 AND THE OCCUPANT LOAD PER TABLE 1004.1.1 THIS |
| | INFORMATION IS REQUIRED SO THAT ANY ADDITIONAL |
| | CONSTRUCTION WILL BE IN ACCORDANCE WITH THE ORIGINAL |
| | BUILDING TYPE. |
| | |
| | |
| | 6) 2007 FBC (EXISTING) 401.4 A DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF |
| | THIS CODE. THIS INFORMATION SHALL BE INDICATED ON THE |
| | PLANS. |
| | |
| | 7) SUBMIT A CEILING PLANS SHOWING THE LAYOUT OF THE |
| | LIGHTING AND SPRINKLER HEADS IN RELATION THE TO THE NEW |
| | OFFICES 106.3.5.1.1(5) |
| | |
| | 8) THE DOOR SCHEDULE INDICATES DOOR #2 AS EXISTING. HOW |
| | IS THIS POSSIBLE IF THERE NO EXISTING WALL? CLARIFY. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561)805-6726 |
| | FAX (561) 805-6731 |
| | |