| 2009-08-28 10:15:36 | ** TEMPORARY FAILED** |
| | |
| | 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS FOR LIGHTING |
| | PERFORMANCE CALCULATIONS ARE NOT SEALED BY THE DESIGN |
| | PROFESSIONAL AS REQUIRED PER FS 481.221/471.025. |
| | BOTH COPIES ARE SIGNED AND DATED. CALLED AND LEFT |
| | MESSAGE ON ARCHITECT*S CELL PHONE. |
| | |
| | |
| | |
| | ** PROVISO/REDLINED PLANS** |
| | |
| | *** THE FOLLOWING ARE SET FORTH AS A PROVISO. ALL |
| | REVISIONS AND CORRECTIONS SHALL BE MADE BEFORE FINAL |
| | INSPECTIONS AND SOME ITEMS MUST BE DONE BE TCO. |
| | |
| | |
| | ** SPOKE TO ARCHITECT, CORRECTIONS WILL MOST LIKELY BE |
| | SUBMITTED ON MONDAY 8/31 AS CORRECTED REVISIONS INSTEAD |
| | OF PROVISO. |
| | |
| | 1) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK |
| | INCLUDING ALL LABOR, MATERIALS, EQUIPMENT MUST BE |
| | UPDATED. THE INCREASE IN THE ELECTRICAL SCOPE OF WORK, |
| | EQUIPMENT AND MATERIALS IS SUBSTANTIAL. PROVIDE ALL |
| | SIGNED, CONTRACTS, EQUIPMENT, MATERIAL INVOICES OR |
| | ADJUST VALUE ACCORDINGLY TO APPROPRIATE VALUE. |
| | FBC 108.3 |
| | |
| | 2) NOTE: TO DATE AFTER PREVIOUS REVIEWS AND MEETING THE |
| | MINIMUM LEVELS, HEIGHTS, INTENSITY OF HORN, STROBES, |
| | HORN/STROBE DEVICES IS STILL NOT SHOWN ON PLANS MEETING |
| | MINIMUM COMPLIANCE FOR ADA. PLEASE SEE FBC 11-4.28.1,.2 |
| | AND .3(4) |
| | ** TO DATE NO FIRE ALARM PERMIT HAS BEEN APPLIED. |
| | BASE PLANS MUST SHOW MINIMUM DESIGN REQUIRED FOR LIFE |
| | SAFETY AND OTHER APPLICABLE CODES. FS 633 |
| | |
| | 3) NOTE: THE OCCUPANCY SENSORS IN RECEIVING AREA ON |
| | LIGHTING PLANS ARE NOT THE SAME AS SHOWN ON E2.1. PLANS |
| | SHOW WITH CEILING DEVICES ON E-2 AND WALL DEVICES ON |
| | SHEET E2.1. |
| | |
| | 4) NOTE: THE RECESSED LIGHTS AT FRONT ENTRANCE STILL |
| | INDICATE TO A PANEL P2. HOWEVER THIS SHOULD BE P-2. |
| | SPOKE TO ARCHITECT. |
| | 408.4, 310.16. |
| | |
| | 5) NOTE: LOADS SHOWN ON PANEL P WHICH FEED PANEL P-1 DO |
| | NOT COORDINATE. LOAD ON P-1 IS HIGHER THAN LOAD ON |
| | PANEL P. |
| | THE CALCULATIONS ON P-1 INDICATE LOAD AT 125% HOWEVER |
| | THE LOAD ON PANEL IS HIGHER THAN THE TOTAL. PANEL |
| | INDICATES 8400 AND THE CALCULATION AFTER THE 125% IS |
| | ONLY AT 8000. |
| | PLEASE EXPLAIN LOAD SHOWN ON MDP FOR PANEL P WHICH IS |
| | SHOWN AT 8600VA. |
| | ** BOTH OF THESE ITEMS WERE GONE OVER IN PREVIOUS |
| | MEETING. |
| | 215.3,230.42, 220, 408.4 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS. |
| | |
| | 6) NOTE: THE METHOD OF CONTROLS ON THE IDR IS STILL |
| | SHOWN AS MANUAL ON/OFF. |
| | 13-415.B.1. |
| | |
| | 7) NOTE: NEW 600AMP MAIN DISCONNECT INDICATES A NEW |
| | SEPARATE GROUNDING ELECTRODE SYSTEM HOWEVER AS THIS |
| | MAIN IS TAPPED FROM EXISTING GUTTED THE GROUNDING |
| | ELECTRODE SYSTEM IS ALREADY EXISTING DONE UNDER THE |
| | SHELL PERMIT. IF ADDING ADDITIONAL GROUNDING ELECTRODE |
| | CONDUCTOR AND GROUNDING ELECTRODE THEN THESE MUST BE |
| | BONDED TO THE EXISTING SYSTEM. |
| | PLEASE VERIFY THIS AND REVISE AS NEEDED. |
| | 250.50, 220.58 |
| | |
| | |
| | **** IMPORTANT: |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |