Plan Review Notes
Plan Review Notes For Permit 09030496
Permit Number 09030496
Review Stop E
Sequence Number 6
Notes
Date Text
2009-08-28 10:15:36** TEMPORARY FAILED**
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS FOR LIGHTING
 PERFORMANCE CALCULATIONS ARE NOT SEALED BY THE DESIGN
 PROFESSIONAL AS REQUIRED PER FS 481.221/471.025.
 BOTH COPIES ARE SIGNED AND DATED. CALLED AND LEFT
 MESSAGE ON ARCHITECT*S CELL PHONE.
  
  
  
 ** PROVISO/REDLINED PLANS**
  
 *** THE FOLLOWING ARE SET FORTH AS A PROVISO. ALL
 REVISIONS AND CORRECTIONS SHALL BE MADE BEFORE FINAL
 INSPECTIONS AND SOME ITEMS MUST BE DONE BE TCO.
  
  
 ** SPOKE TO ARCHITECT, CORRECTIONS WILL MOST LIKELY BE
 SUBMITTED ON MONDAY 8/31 AS CORRECTED REVISIONS INSTEAD
 OF PROVISO.
  
 1) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK
 INCLUDING ALL LABOR, MATERIALS, EQUIPMENT MUST BE
 UPDATED. THE INCREASE IN THE ELECTRICAL SCOPE OF WORK,
 EQUIPMENT AND MATERIALS IS SUBSTANTIAL. PROVIDE ALL
 SIGNED, CONTRACTS, EQUIPMENT, MATERIAL INVOICES OR
 ADJUST VALUE ACCORDINGLY TO APPROPRIATE VALUE.
 FBC 108.3
  
 2) NOTE: TO DATE AFTER PREVIOUS REVIEWS AND MEETING THE
 MINIMUM LEVELS, HEIGHTS, INTENSITY OF HORN, STROBES,
 HORN/STROBE DEVICES IS STILL NOT SHOWN ON PLANS MEETING
 MINIMUM COMPLIANCE FOR ADA. PLEASE SEE FBC 11-4.28.1,.2
 AND .3(4)
 ** TO DATE NO FIRE ALARM PERMIT HAS BEEN APPLIED.
 BASE PLANS MUST SHOW MINIMUM DESIGN REQUIRED FOR LIFE
 SAFETY AND OTHER APPLICABLE CODES. FS 633
  
 3) NOTE: THE OCCUPANCY SENSORS IN RECEIVING AREA ON
 LIGHTING PLANS ARE NOT THE SAME AS SHOWN ON E2.1. PLANS
 SHOW WITH CEILING DEVICES ON E-2 AND WALL DEVICES ON
 SHEET E2.1.
  
 4) NOTE: THE RECESSED LIGHTS AT FRONT ENTRANCE STILL
 INDICATE TO A PANEL P2. HOWEVER THIS SHOULD BE P-2.
 SPOKE TO ARCHITECT.
 408.4, 310.16.
  
 5) NOTE: LOADS SHOWN ON PANEL P WHICH FEED PANEL P-1 DO
 NOT COORDINATE. LOAD ON P-1 IS HIGHER THAN LOAD ON
 PANEL P.
 THE CALCULATIONS ON P-1 INDICATE LOAD AT 125% HOWEVER
 THE LOAD ON PANEL IS HIGHER THAN THE TOTAL. PANEL
 INDICATES 8400 AND THE CALCULATION AFTER THE 125% IS
 ONLY AT 8000.
 PLEASE EXPLAIN LOAD SHOWN ON MDP FOR PANEL P WHICH IS
 SHOWN AT 8600VA.
 ** BOTH OF THESE ITEMS WERE GONE OVER IN PREVIOUS
 MEETING.
 215.3,230.42, 220, 408.4
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 6) NOTE: THE METHOD OF CONTROLS ON THE IDR IS STILL
 SHOWN AS MANUAL ON/OFF.
 13-415.B.1.
  
 7) NOTE: NEW 600AMP MAIN DISCONNECT INDICATES A NEW
 SEPARATE GROUNDING ELECTRODE SYSTEM HOWEVER AS THIS
 MAIN IS TAPPED FROM EXISTING GUTTED THE GROUNDING
 ELECTRODE SYSTEM IS ALREADY EXISTING DONE UNDER THE
 SHELL PERMIT. IF ADDING ADDITIONAL GROUNDING ELECTRODE
 CONDUCTOR AND GROUNDING ELECTRODE THEN THESE MUST BE
 BONDED TO THE EXISTING SYSTEM.
 PLEASE VERIFY THIS AND REVISE AS NEEDED.
 250.50, 220.58
  
  
 **** IMPORTANT:
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  