Plan Review Notes
Plan Review Notes For Permit 09030496
Permit Number 09030496
Review Stop E
Sequence Number 5
Notes
Date Text
2009-08-21 13:57:49 
 ** DENIED REVISION **
  
 ** ELECTRICAL PERMIT ISSUED TO DATE IS ONLY FOR
 ELECTRICAL CONDUITS IN SLAB.
  
 ** SEPARATE PERMIT(S) STILL REQUIRED FOR LV.
  
 ** NO FIRE ALARM PERMIT HAS BEEN APPLIED/OR SUBMITTED.
 SEE NOTES BELOW WITH RESPECT TO MINIMUM FBC ADA
 REQUIREMENTS.
  
 1) NOTE: PLANS SUBMITTED CONTAIN *WHITE-OUT* AND HAND
 DRAWN CHANGES TO PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ENGINEER. THIS IS NOT PERMITTED.
 PLANS SHALL BE REVISED, SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD.
 FS 471
 PLEASE ALSO SEE FAC 61G15-23.002.
  
 2) NOTE: THE LIGHTING CONTROLS ON PLANS STILL DO NOT
 MEET THE FLORIDA BUILDING CODE MINIMUM.
 13-415.AB.1.1,.1.2, .1.3 AND .1.4
  
 A) THE POWER PLANS STILL INDICATE STANDARD SINGLE POLE
 SWITCHES FOR LIGHTING CONTROLS.
  
 B) THERE ARE OTHER STANDARD SWITCH DEVICES SHOWN FOR
 OTHER ITEMS SUCH AS REAR EXTERIOR LIGHTS WHICH IS NOT
 PERMITTED.
  
 C) ZONES, AND OVER RIDES PER SECTIONS GIVEN ARE NOT
 SHOWN ON PLANS. IN FACT THE PLANS DO NOT INDICATE ANY
 SPECIFIC DETAILS OR MINIMUMS. THE RISER NOTES MENTIONS
 TO SEE LEGEND FOR DETAILS HOWEVER THERE ARE NO
 DETAILS??
  
 D) OVER RIDES FOR THE OCCUPANTS AND MAXIMUM OVER RIDE
 TIMES ARE NOT SHOWN. AN OCCUPANT MUST SEE ALL LIGHTING
 WHICH IS BEING OVER RIDDEN OR MEET EXCEPTIONS. IF
 MEETING EXCEPTIONS, THEN PLEASE BE SURE TO SHOW
 INFORMATION ON PLANS.
 PLEASE BE SURE ZONES FOR MAXIMUM SPACE CONTROLS ARE
 SHOWN. PLEASE BE SURE TO THE LOCATIONS ARE SHOWN.
  
 E) THERE ARE SOME OCCUPANCY SENSOR DEVICES SHOWN ON
 SYMBOL LEGEND. HOWEVER NONE OF THESE DEVICES ARE SHOWN
 ON PLANS.
  
 F) SOME DEVICES STATE *SWITCH/ TIMER*. SEE FBC CHAPTER
 11 FOR ADA COMPLIANCE. TWIST TYPE TIMERS ARE NOT
 PERMITTED. 11.4-.27.4
  
  
  
 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS DO NOT MEET THE MINIMUM PER FBC
 13-415.AB.5.
 THERE IS ANOTHER NEW SUBMITTED METHOD *B* HOWEVER THE
 METHOD *B* SUBMITTED IS FOR SHELL ONLY. THIS IS NOT A
 SHELL. THIS IS A TENANT BUILDING OUT. THE DESIGN AND
 CRITERIA WILL BE LISTED ON THE SUMMARY SHEETS.
 PLEASE SEE 13-400.B.0.4, 13-415.B.1, .2.2 ETC
 *** PLEASE CALL TO GO OVER CALCULATIONS.
 THE EXTERIOR LIGHTS ON THE IDR INDICATES ONE FIXTURE AT
 2000WATTS. THIS IS NOT POSSIBLE.
 PLEASE ALSO SEE THAT ALL SPACES NEED TO BE SHOWN. OTHER
 SPACES SUCH AS STORAGE CLOSETS AND OTHER AREAS ARE NOT
 SHOWN.
 ** FIXTURE LEGEND NEEDS TO BE COMPLETED WITH ALL
 SPECIFIC FIXTURES. STATING A 1X4 FLUORESCENT FIXTURE OR
 2X4 FIXTURE DOES NOT GIVE INFORMATION NEEDED. THESE
 COULD HAVE WATTAGES OF 28, 32 , 64, 56, 86, 92, 96,
 110, 120, OR GREATER. SEE E-3 FOR EXAMPLE; FIXTURE
 LISTED FOR * BACK OFFICES STATES THERE ARE 2-32WATT
 BULBS WITH A POWER FACTOR OF 1.1, YET THE TOTAL PER
 FIXTURE IS SHOWN AS 35.2. THIS IS NOT POSSIBLE.
 A FIXTURE WITH 2-32W BULBS WITH A POWER FACTOR OF 1.1
 WOULD BE A TOTAL FIXTURE VA OF 70.4 PER FIXTURE, NOT
 35.2. THIS WOULD BRING THE TOTAL UP TO 140.8WATTS.
 ** PLEASE GO OVER ALL OF THE FIXTURES, OBTAIN SPECIFIC
 INFORMATION AND ADJUST.
  
 ** PLEASE SEE THE IDR OF THE SUBMITTED ENERGY
 CALCULATIONS. THE CONTROLS ARE SHOWN AS *MANUAL
 ON/OFF*. THIS WOULD BE BASED ON THE TYPE OF CONTROLS
 FOR EACH SPACE ON PLANS. IE: TIME SCHEDULING, OCCUPANCY
 SENSORS ETC.
  
 ** CALL IF THERE ARE QUESTIONS.
  
  
 5) NOTE: PLEASE SEE 250.20,250.30,250.50, AS THE
 PREVIOUS PLANS STATED THE GEC TO CWP AND GROUND ROD FOR
 TRANSFORMER ATTACHMENT. HOWEVER PER SECTIONS ABOVE,
 BUILDING STEEL WAS NOTED AS BEING REQUIRED. NOW THE
 RISER WAS REVISE REMOVING CWP ??
  
 6) NOTE: SHOW WINDOW LOADS NEED TO BE SHOWN PER 220.14,
 220.43
 LOAD CALCULATIONS SUBMITTED STILL DO NOT MEET NEC
 SECTION 220.
 220.12,220.14,220.42,220.44 ETC
  
 7) NOTE: TO DATE NO FIRE ALARM PERMIT APPLICATION HAS
 BEEN SUBMITTED. THE DEVICES INSTALLED ON SHELL PERMIT
 WERE ONLY FOR SHELL. WITH THE INSTALLATION OF WALLS AND
 OTHER OBSTACLES THE DEVICE LOCATIONS SHOWN AND
 INSTALLED ON SHELL DO NOT MEET MINIMUM FOR ADA FOR
 TENANT BUILD OUT. PLEASE SEE FBC 11-4.28.1,.2 AND .3
 FOR MINIMUM LOCATIONS, HEIGHTS, LEVELS, CANDELA LEVELS,
 DB LEVELS ETC.
 LOCATIONS SUCH AS RECEIVING, BATHROOMS, RETAIL SALES
 FLOOR AREAS, OFFICE ETC.
  
 8) NOTE: PLANS ARE NOW SHOWING A COMPLETELY NEW
 SERVICE. THIS IS NOT PERMITTED. THE SHELL BUILDING HAD
 SERVICE FOR BUILDING AND EQUIPMENT/MAINS FOR FUTURE
 TENANTS. NOW RISER INDICATES A NEW SERVICE. PLEASE SHOW
 ALL SERVICE EQUIPMENT, RISER EQUIPMENT ETC AS
 PREVIOUSLY REQUESTED. PLEASE BE SURE TO OBTAIN
 ELECTRICAL RISER INFORMATION FROM SHELL PLANS.
 PLEASE ADJUST EQUIPMENT AND SERVICE. 230.2E,
 230.70,230.71,230.72. PLEASE SHALL LOCATIONS OF ALL
 MAINS.
  
 9) NOTE: THIS NOTE REMAINS AS PLANS CONTAINS *WHITE
 OUT* FOR REVISING THIS INFORMATION.
 THE PANEL ON THE SECONDARY SIDE OF THE TRANSFORMER DOES
 NOT INDICATE ANY MAIN. ALL TAPPED CONDUCTORS SHALL
 TERMINATE IN OVER CURRENT PROTECTION. 240.21. PLEASE
 ALSO SEE 408.36, 240.4, 310.16 ETC
  
 10) NOTE: PLANS NOW INDICATE SHOW WINDOW RECEPTACLES ON
 A PANEL SCHEDULE P1, HOWEVER THE CIRCUITING ON PLANS
 INDICATES CIRCUITS TO PANEL *P*> SUCH AS *P-38, P-40.
 NEITHER PANEL *P* NOR PANEL *P1* HAVE ANY CIRCUITS 38,
 OR 40 FOR SHOW WINDOWS.
 THE FACT IS THAT PANEL *P* SHOWS SPARES CIRCUITS FOR 38
 AND 40, AND PANEL P1 IS ONLY SHOWN AS A 24 CIRCUIT
 PANEL.
  
 11) NOTE: NO EGRESS LIGHTING SHOWN ON PLANS FOR
 RECEIVING AREA? PLEASE SEE FBC CHAPTER 10, NFPA-101
 LIFE SAFETY CODE 7.8.1.3, 7.9.1.2, .2.2. PLEASE SEE
 700.12F FOR CIRCUITING TO LOCAL LIGHTING BRANCH
 CIRCUITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  