| Date |
Text |
| 2009-08-21 13:57:49 | |
| | ** DENIED REVISION ** |
| | |
| | ** ELECTRICAL PERMIT ISSUED TO DATE IS ONLY FOR |
| | ELECTRICAL CONDUITS IN SLAB. |
| | |
| | ** SEPARATE PERMIT(S) STILL REQUIRED FOR LV. |
| | |
| | ** NO FIRE ALARM PERMIT HAS BEEN APPLIED/OR SUBMITTED. |
| | SEE NOTES BELOW WITH RESPECT TO MINIMUM FBC ADA |
| | REQUIREMENTS. |
| | |
| | 1) NOTE: PLANS SUBMITTED CONTAIN *WHITE-OUT* AND HAND |
| | DRAWN CHANGES TO PLANS WHICH ARE SIGNED, DATED AND |
| | SEALED BY AN ENGINEER. THIS IS NOT PERMITTED. |
| | PLANS SHALL BE REVISED, SIGNED, DATED AND SEALED BY THE |
| | ENGINEER OF RECORD. |
| | FS 471 |
| | PLEASE ALSO SEE FAC 61G15-23.002. |
| | |
| | 2) NOTE: THE LIGHTING CONTROLS ON PLANS STILL DO NOT |
| | MEET THE FLORIDA BUILDING CODE MINIMUM. |
| | 13-415.AB.1.1,.1.2, .1.3 AND .1.4 |
| | |
| | A) THE POWER PLANS STILL INDICATE STANDARD SINGLE POLE |
| | SWITCHES FOR LIGHTING CONTROLS. |
| | |
| | B) THERE ARE OTHER STANDARD SWITCH DEVICES SHOWN FOR |
| | OTHER ITEMS SUCH AS REAR EXTERIOR LIGHTS WHICH IS NOT |
| | PERMITTED. |
| | |
| | C) ZONES, AND OVER RIDES PER SECTIONS GIVEN ARE NOT |
| | SHOWN ON PLANS. IN FACT THE PLANS DO NOT INDICATE ANY |
| | SPECIFIC DETAILS OR MINIMUMS. THE RISER NOTES MENTIONS |
| | TO SEE LEGEND FOR DETAILS HOWEVER THERE ARE NO |
| | DETAILS?? |
| | |
| | D) OVER RIDES FOR THE OCCUPANTS AND MAXIMUM OVER RIDE |
| | TIMES ARE NOT SHOWN. AN OCCUPANT MUST SEE ALL LIGHTING |
| | WHICH IS BEING OVER RIDDEN OR MEET EXCEPTIONS. IF |
| | MEETING EXCEPTIONS, THEN PLEASE BE SURE TO SHOW |
| | INFORMATION ON PLANS. |
| | PLEASE BE SURE ZONES FOR MAXIMUM SPACE CONTROLS ARE |
| | SHOWN. PLEASE BE SURE TO THE LOCATIONS ARE SHOWN. |
| | |
| | E) THERE ARE SOME OCCUPANCY SENSOR DEVICES SHOWN ON |
| | SYMBOL LEGEND. HOWEVER NONE OF THESE DEVICES ARE SHOWN |
| | ON PLANS. |
| | |
| | F) SOME DEVICES STATE *SWITCH/ TIMER*. SEE FBC CHAPTER |
| | 11 FOR ADA COMPLIANCE. TWIST TYPE TIMERS ARE NOT |
| | PERMITTED. 11.4-.27.4 |
| | |
| | |
| | |
| | 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE |
| | CALCULATIONS DO NOT MEET THE MINIMUM PER FBC |
| | 13-415.AB.5. |
| | THERE IS ANOTHER NEW SUBMITTED METHOD *B* HOWEVER THE |
| | METHOD *B* SUBMITTED IS FOR SHELL ONLY. THIS IS NOT A |
| | SHELL. THIS IS A TENANT BUILDING OUT. THE DESIGN AND |
| | CRITERIA WILL BE LISTED ON THE SUMMARY SHEETS. |
| | PLEASE SEE 13-400.B.0.4, 13-415.B.1, .2.2 ETC |
| | *** PLEASE CALL TO GO OVER CALCULATIONS. |
| | THE EXTERIOR LIGHTS ON THE IDR INDICATES ONE FIXTURE AT |
| | 2000WATTS. THIS IS NOT POSSIBLE. |
| | PLEASE ALSO SEE THAT ALL SPACES NEED TO BE SHOWN. OTHER |
| | SPACES SUCH AS STORAGE CLOSETS AND OTHER AREAS ARE NOT |
| | SHOWN. |
| | ** FIXTURE LEGEND NEEDS TO BE COMPLETED WITH ALL |
| | SPECIFIC FIXTURES. STATING A 1X4 FLUORESCENT FIXTURE OR |
| | 2X4 FIXTURE DOES NOT GIVE INFORMATION NEEDED. THESE |
| | COULD HAVE WATTAGES OF 28, 32 , 64, 56, 86, 92, 96, |
| | 110, 120, OR GREATER. SEE E-3 FOR EXAMPLE; FIXTURE |
| | LISTED FOR * BACK OFFICES STATES THERE ARE 2-32WATT |
| | BULBS WITH A POWER FACTOR OF 1.1, YET THE TOTAL PER |
| | FIXTURE IS SHOWN AS 35.2. THIS IS NOT POSSIBLE. |
| | A FIXTURE WITH 2-32W BULBS WITH A POWER FACTOR OF 1.1 |
| | WOULD BE A TOTAL FIXTURE VA OF 70.4 PER FIXTURE, NOT |
| | 35.2. THIS WOULD BRING THE TOTAL UP TO 140.8WATTS. |
| | ** PLEASE GO OVER ALL OF THE FIXTURES, OBTAIN SPECIFIC |
| | INFORMATION AND ADJUST. |
| | |
| | ** PLEASE SEE THE IDR OF THE SUBMITTED ENERGY |
| | CALCULATIONS. THE CONTROLS ARE SHOWN AS *MANUAL |
| | ON/OFF*. THIS WOULD BE BASED ON THE TYPE OF CONTROLS |
| | FOR EACH SPACE ON PLANS. IE: TIME SCHEDULING, OCCUPANCY |
| | SENSORS ETC. |
| | |
| | ** CALL IF THERE ARE QUESTIONS. |
| | |
| | |
| | 5) NOTE: PLEASE SEE 250.20,250.30,250.50, AS THE |
| | PREVIOUS PLANS STATED THE GEC TO CWP AND GROUND ROD FOR |
| | TRANSFORMER ATTACHMENT. HOWEVER PER SECTIONS ABOVE, |
| | BUILDING STEEL WAS NOTED AS BEING REQUIRED. NOW THE |
| | RISER WAS REVISE REMOVING CWP ?? |
| | |
| | 6) NOTE: SHOW WINDOW LOADS NEED TO BE SHOWN PER 220.14, |
| | 220.43 |
| | LOAD CALCULATIONS SUBMITTED STILL DO NOT MEET NEC |
| | SECTION 220. |
| | 220.12,220.14,220.42,220.44 ETC |
| | |
| | 7) NOTE: TO DATE NO FIRE ALARM PERMIT APPLICATION HAS |
| | BEEN SUBMITTED. THE DEVICES INSTALLED ON SHELL PERMIT |
| | WERE ONLY FOR SHELL. WITH THE INSTALLATION OF WALLS AND |
| | OTHER OBSTACLES THE DEVICE LOCATIONS SHOWN AND |
| | INSTALLED ON SHELL DO NOT MEET MINIMUM FOR ADA FOR |
| | TENANT BUILD OUT. PLEASE SEE FBC 11-4.28.1,.2 AND .3 |
| | FOR MINIMUM LOCATIONS, HEIGHTS, LEVELS, CANDELA LEVELS, |
| | DB LEVELS ETC. |
| | LOCATIONS SUCH AS RECEIVING, BATHROOMS, RETAIL SALES |
| | FLOOR AREAS, OFFICE ETC. |
| | |
| | 8) NOTE: PLANS ARE NOW SHOWING A COMPLETELY NEW |
| | SERVICE. THIS IS NOT PERMITTED. THE SHELL BUILDING HAD |
| | SERVICE FOR BUILDING AND EQUIPMENT/MAINS FOR FUTURE |
| | TENANTS. NOW RISER INDICATES A NEW SERVICE. PLEASE SHOW |
| | ALL SERVICE EQUIPMENT, RISER EQUIPMENT ETC AS |
| | PREVIOUSLY REQUESTED. PLEASE BE SURE TO OBTAIN |
| | ELECTRICAL RISER INFORMATION FROM SHELL PLANS. |
| | PLEASE ADJUST EQUIPMENT AND SERVICE. 230.2E, |
| | 230.70,230.71,230.72. PLEASE SHALL LOCATIONS OF ALL |
| | MAINS. |
| | |
| | 9) NOTE: THIS NOTE REMAINS AS PLANS CONTAINS *WHITE |
| | OUT* FOR REVISING THIS INFORMATION. |
| | THE PANEL ON THE SECONDARY SIDE OF THE TRANSFORMER DOES |
| | NOT INDICATE ANY MAIN. ALL TAPPED CONDUCTORS SHALL |
| | TERMINATE IN OVER CURRENT PROTECTION. 240.21. PLEASE |
| | ALSO SEE 408.36, 240.4, 310.16 ETC |
| | |
| | 10) NOTE: PLANS NOW INDICATE SHOW WINDOW RECEPTACLES ON |
| | A PANEL SCHEDULE P1, HOWEVER THE CIRCUITING ON PLANS |
| | INDICATES CIRCUITS TO PANEL *P*> SUCH AS *P-38, P-40. |
| | NEITHER PANEL *P* NOR PANEL *P1* HAVE ANY CIRCUITS 38, |
| | OR 40 FOR SHOW WINDOWS. |
| | THE FACT IS THAT PANEL *P* SHOWS SPARES CIRCUITS FOR 38 |
| | AND 40, AND PANEL P1 IS ONLY SHOWN AS A 24 CIRCUIT |
| | PANEL. |
| | |
| | 11) NOTE: NO EGRESS LIGHTING SHOWN ON PLANS FOR |
| | RECEIVING AREA? PLEASE SEE FBC CHAPTER 10, NFPA-101 |
| | LIFE SAFETY CODE 7.8.1.3, 7.9.1.2, .2.2. PLEASE SEE |
| | 700.12F FOR CIRCUITING TO LOCAL LIGHTING BRANCH |
| | CIRCUITS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |